88SN0062
~er~e-~~r-X988-6g6
3~~y-~9;-}988-6P6
July 27, 1988 BS
REQUEST ANALYSIS
AND
RECOMMENDATION
88SN0062
Contel Cellular, Inc.
Midlothian Magisterial District
East line of North Providence Road
REQUEST: Conditional Use Planned Development to permit a 198 foot communica-
tions tower in a Community Business (B-2) District. A sixty-eight
(68) foot exception to the eighty-one (81) foot rear yard setback
requirement for the 198 foot tower and a ten (10) foot exception to
the thirty (30) foot rear yard setback for an associated equipment
building are also requested.
PLANNING COMMISSION RECOMMENDATION
RECOMMEND DENIAL.
STAFF RECOMMENDATION
Recommend approval for the following reasons:
A. The subject property is currently zoned Community Business (B-2) and
as such could be developed for a variety of commercial uses. In
addition, adjacent properties are zoned commercially and have been
developed for commercial uses. The proposed tower will not generate
excessive traffic or noise and will have minimal impact upon area
development.
B. Similar communications towers have been erected in the area without
any apparent adverse impact upon adjacent commercial properties.
C. The conditions recommended herein will further minimize the pos-
sibility of any adverse impact upon area development, the
Chesterfield County Public Safety Trunked System, or the County
Airport.
(NOTE: THE CONDITIONS NOTED WITH "STAFF/CPC" WERE AGREED UPON BY BOTH STAFF
AND THE COMMISSION. CONDITIONS WITH ONLY A "STAFF" ARE RECOMMENDED SOLELY BY
STAFF. CONDITIONS WITH ONLY A "CPC" ARE ADDITIONAL CONDITIONS RECOMMENDED BY
THE PLANNING COMMISSION.)
CONDITIONS
(STAFF) 1. The plan prepared by Potts and Minter, dated March 14, 1988,
shall be considered the Master Plan. (P)
(STAFF) 2. This Conditional Use Planned Development shall be granted for
the purpose of constructing a 198 foot tower and an equipment
building. (P)
(STAFF) 3. All driveways and parking areas shall be graveled and main-
tained to minimize dust problems and provide ease of ingress
and egress. (P)
(STAFF) 4. There shall be no signs permitted to identify this use. (P)
(STAFF) 5. The base of the tower shall be enclosed by a six (6) foot high
fence, designed to preclude trespassing. The fence shall be
placed so as to provide sufficient room between the fence and
property line to accommodate evergreen planting having an
initial height and spacing to provide screening of the base of
the tower and the equipment building from adjacent properties.
Further, existing vegetation located between the fence and the
property lines shall be retained, where possible, to provide
further screening of the base of the tower. A detailed plan
depicting this requirement shall be submitted to the Planning
Department for approval in conjunction with final site plan
review. (P)
(STAFF) 6. Prior to release of a building permit for the tower, a copy of
FAA approval shall be submitted to the Planning Department.
(P)
(STAFF) 7. The tower and equipment shall be designed and installed so as
not to interfere with the Chesterfield County Public Safety
Trunked System. Prior to release of a building permit, the
applicants shall perform an engineering study to determine the
possibility of radio frequency interference with the County
system and the study shall be submitted to the Chesterfield
County's Communications and Electronics staff for review and
approval. (FD)
(STAFF) 8. The developer shall be responsible for correcting any frequency
problems which affect the Chesterfield County Public Safety
Trunked System. Such corrections shall be made immediately
upon notification of any problems by the Chesterfield County
Communications and Electronics staff. (FD)
(STAFF) 9. Prior to the issuance of a building permit, thirty-five (35)
feet of right of way, measured from the centerline of North
Providence Road, shall be dedicated to and for the County of
Chesterfield, free and unrestricted. (T)
(STAFF) 10. In conjunction with the
Commission shall grant
Plan. (P)
approval of this request, the Planning
schematic plan approval of the Master
2 "~$N0062/BSJUL$/JULY27U
GENERAL INFORMATION
Location: East line of North Providence Road, approx-
imately 200 feet north of Midlothian Turn-
pike. Tax Map 18-15 (1) Parcel 15 (Sheet
8).
Existing Zoning: B-2
Size: 0.4 acres
Existing Land Use: Vacant
Adjacent Zoning & Land Use: North - B-2; Commercial
South - B-2; Commercial
East - B-3; Commercial
West - B-2 and B-2 with Conditional Use
Planned Development; Commercial
Utilities: Public water and sewer not required for
proposed use.
Environmental Engineering: Drains through easements to tributaries of
Pocoshock Creek. There are existing off-
site drainage problems downstream at
Cloverleaf Lake Apartments, which experi-
ences occasional flooding. The proposed
improvements will generate low runoff and
will not adversely affect surrounding
properties. No on- or off-site drainage
and/or erosion control problems anticipated
with this development.
Fire Service: Buford Fire Station, Company 4~9. At pre-
sent, fire service capability adequate.
General Plan
(Northern Area Land
Use and Transporta-
tion Plan): General commercial
Transportation: Proposed use will have minimal impact on
area traffic patterns. The Northern Area
Land Use and Transportation Plan identifies
North Providence Road as a collector with a
recommended right of way width of seventy
(70) feet. Right of way should be dedicat-
ed in accordance with the Plan.
DISCUSSION
A Conditional Use Planned Development is requested with the intent of
erecting a 198 foot tower and equipment building. The planned facilities
3 88SN0062/BSJUL8/JULY27U
will provide cellular phone communications. The facility will be visited
occasionally by maintenance personnel, but otherwise will be unmanned.
Exceptions to the rear yard setback requirement for the tower and associ-
ated equipment building are also requested.
The area surrounding the request parcel is characterized by commercial
development and the Northern Area Land Use and Transportation Plan desig-
nates the site for heavy commercial use. The property is currently zoned
Community Business (B-2) and could be developed for those uses permitted
in that District. The proposed tower will not generate traffic and noise
which is usually associated with uses permitted by B-2 zoning. Through
the Conditional Use Planned Development process, the Commission and Board
can impose conditions that further ensure appropriate land use com-
patibility with existing area commercial uses. The recommended con-
ditions are designed to ensure that the facility will not adversely
affect the surrounding area. (Conditions 3, 4, and 5)
It should be noted that similar communications towers currently exist in
the area without any apparent adverse impact upon adjacent commercial
land uses. Specifically, a 100 foot tower is currently located on prop-
erty fronting Buford Road to the east within 550 feet of the proposed
facilities. In addition, a 430 foot tower has been erected on State
Police Headquarters property fronting Midlothian Turnpike to the east.
The County Airport Manager has indicated that the tower will not adverse-
ly affect the County's airport operations. The Chesterfield County
emergency radio personnel have reviewed this request and indicated that
the proposed tower and equipment should be designed so as not to inter-
fere with the Chesterfield County Public Safety Trunked System (Condition
7). Once the facility is in operation, the developer should be required
to correct any problems should they arise. (Condition 8)
The requested setback exceptions should not have any adverse impact upon
adjacent commercial development to the north, east and south. Therefore,
approval of these exceptions would be appropriate.
CASE HISTORY
Planning Commission Meeting (6/21/88):
At the request of the applicant, the Commission deferred this case for
thirty (30) days to allow the applicant an opportunity to meet with area
property owners.
Staff (6/22/88):
The applicant was advised in writing that any new information must be
submitted no later than June 27, 1988, in order to be considered at the
July 19, 1988, Zoning Session.
4 ^~N0062/BSJUL8/JULY27U
Staff (6/27/88):
To date, no new information has been submitted.
Planning Commission Meeting (7/19/88):
The applicant accepted the recommendation.
There was opposition present. Concerns centered around whether or not
the tower would present a safety problem for area business establishments
and more particularly a day care center.
On motion of Mr. Kelly, seconded by Mr. Warren, the Commission recommend-
ed denial of this request.
AYES: Unanimous.
The Board of Supervisors on Wednesday, July 27, 1988, beginning at 2:00 p.m.,
will take under consideration this request.
5 88SN0062/BSJUL8/JULY27U
y ~ 1
OWN/TF CI7EfX ~
'' • _
R-7
Q= ,''''',~ Cc ,',,','~~~ .~
~~ R CKCREEK PARK ~~`~
V o ~ ~~,j', ~ ` ~
,•~• y .~
s
y ~ R-TH •. ~ ~ c
'9 c -~ ~ ~'
~ o ./ it ~ ~ '~~
30' Z V '~
~ i/i FEN ~ .~_ ~ ~, ~ ~ ~I ~ 11
BON AIR HILLS v 0 , j ~ w B-3 ~ 11 ~
2c OP ~'Tl ~ • ';~ 2~ ~
• c ~_ , ~• ': MIDI-~~HI AN Ma''~ S, Ni...~ ~ ` ~ ,`, , ~
~ C ~~ E V ~~~~~Er ~ + 0
PROVIDENCE GREEN ~ ~
~ ~ _5 ~ o ~1 W i
v ,.a~ r~ ~ •~ d ~
~ e
~. ~ y R TH
. c .~•
~-nni~~ ~-~ _ ~ I I i zc
~..
II
~ PENN ACRES T ~~~"' ' R
_ = G PROVIDENCE COURT _ .:; U S TA N G
V
s
i
~~~
0
~;
n
O ~~
OI
I
N
TOIfiEf; -
(HE/GHT /BS)
N~'M OIO E
/B/. Gt7 '
y a { 9~ 9"
~ ~ < ~-~-~
~o ~o ~ ~ ~ ~~ ~~: ~ !
a ~ O a 0 ~ • ~~, '. .
~ ~~ ~ •.
/B~i OD "
EoUiP~r~"
SHELTER
.
. ~~ ; Q.
_
~
; ~-.
,o
.
•.;
• .,~
4/'x:7S X8"_~/GH ~
CHA//3'L //`Jft -FE-/YG6
,Z~6'iY/DE GATES
~~
~a~
<~
,~~
~o~
~^.
~ ~o~.
3
~`
a~
~~
`~
I~ ~-.
885/~[OO~'2-/
i
J. LLOYD CUMBHY, D.D., LTD.
2701 TURNER ROAD
RICHMOND, VIRGINIA 23224
T~-EptiONE 276-8578
July 26, 1988
~}~.~ R. p. Sowers Jr.
Patient First
8110 rTidlothian ~rnpike
Pichrnond, Va. 23235
Dear Sir:
Reference is made to your inquiry concerning the
tower which is installed adjacent to my property at
2701 Turner Ppd. _
I can certainly understand your opposition to a
198 foot tower in your area. Even though the one
adjacent to me is partially screened at ground level
by trees it is still an eye sore and a detriment to the
properties in the area.
Very truly yours
J. Lloyd ~umbey
S L ROBERT S. LOVELACE CO., INC.
MANUFACTURERS REPRESENTATIVE
P. O. BOX 31393 RICHMOND, VIRGINIA 23294 804-747-6030
Pete Sowers July 27. 1988
Patient First Corporation
15 East Franklin Street
Richmond, VA 23219
Re: Lightning induced power line disturbances
Dear Pete,
The erection of a Communications tower near your health care
facility makes it even more imperative that you protect all electronic
equipment with the proper surge suppression and transient elimination
which provides both common mode (line to ground) and normal mode (line
to neutral) noise attenuation. L.E.A.-Dynatech's Kleanline filters and
TE products provide the finest protection of this sort available.
I have included technical papers by Roy Carpenter which support your
concern about lightning induced transients in facilities near radio and
telecommunications towers. According to Peter Carpenter, Roy
Carpenter's son and engineer at Lightning Eliminators and Consultants,
.Inc., Santa Fe Springs, CA., "near" means anything within a quarter mile
radius of the tower, and that the nearer the point of the lightning
strike (the tower), the more severe we can expect the effects to be.
I hope this information is helpful to you in your planning. If you..
require any further information, please don't hesitate to call.
Sincerely,
ROBERT S. LOVELACE CO., INC.
Dick Schini
Sales Engineer
13007 Lakeland Road
Santa Fe Springs, California 90670
(213)946-6886
PROTECTED FACILITIES LISTING
Type of Facility Number Protected
AM Radio Braodcasters 20
FM Broadcasters 18
TV Broadcasters 20
Petroleum Storage 41
Petroleum Products Processors 11
Meterological Data Sites 44
Chlorine Plants 2
Corporate Buildings 13
Computer Centers 5
Communications Facilities 10
Parking Lots 2
Amusement Park 1
Power Generating Plants (Nuclear & Fossil) 6
Space Tracking Stations 4
Launch Complex 1
Substations 3
Energy Control Centers 6
Microwave Sites 8
Transmission Lines (3 sites) 15 Miles
Cooling Towers 32
TV Cable Repeaters 4
Hospital Complex 2
,~
Type of Facility
Explosives Test Sites
Aircraft Parking Terminals
Airport Control Tower
Nuclear Platns
Oil Reservoir
Gas Plants
Earth Stations
Test Facilities (Rocket Sled)
Aircraft Hangers
Air Force Tracking Centers
Waste Processing Plant
Asphalt Plant
Convention Center
Amusement Park Building
Number Protected
2
40+
1
2
2
2
4
4
4
6
2
1
1
1
c
ti
LIGHTNING ELIMINATORS AND CONSULTANTS INC.
Dissipation Arrays
Sales I{istory 1972 - 1986
--------------------------
Customer
-------- Location
-------- Date
---- Description
-----------
KHOF - TV California 12/71 TV Station Transmitter Site
Elgin AFB Florida 5/73 ~ 1200 ft. Comm. Tower
Unocal-Union Oil Indonesia 4/83 4 20 Acre Tank Farm
CKLW Windsor, Ontario 5/73 5 Tower AM Station
NASA-STDN Rosman, NC 9/75 400 Acres Ant. &' Comp.
Warner Cable Harrisonburg, VA 9/73 TV Transponder Site
Florida Power Orlando, FL 11/73 Meterology Tower Site
WED Enterprises Orlando, FL 01/74 100 Acre Parking Lot
gin AFB Florida 03/74 Rocket Test Site
Jersey Power & New Jersey 04/74 Neterology Tower Site
Light
Walt Disneyworld Florida 06/74 Large Building
PEPCO Oyster Creek, NJ 05/74 Meterology Tower Site
Science Assoc. Rochester 06/74 Meterology Tower Site
Kennedy Space Ctr .Florida 07/74 Meterology Tower Site
NASA-STDN Cape Kennedy, FL 02/75 Space Tracking Base Stn.
WKBN Radio Akron, Ohio 08/74 4 Tower AM Site
WSB Radio Atlanta, GA 08/74 600 ft. AM Tower
Penn Power Reading, PA 09/74 Meterology Tower Site
WINZ Radio Miami, FL 11/74 6 Tower AM Station
Florida Power Turkey Point, FL 09/74 Meterology Tower Site
Corporation
Florida Power Orlando, FL 10/74 Elec. Substation
corporation
.imet Colorado 10/74 Meterology Tower Site
~/
-2-
Customer Location
Date Description
Commonwealth Chicago, IL
Edison
Dayton Power & Dayton, Ohio
Light
WED Enterprises Orlando, FL
Ponce Broadctg. Puerto Rico
Allied General South Carolina
Florida Power & Ft. Lauderdale, FL
Light
NASA - Launch #41 Cape Kennedy, FL
WDBO - Radio Orlando, FL
Carolina Power North Carolina
Union Electric St. Louis, MO
E. I. DuPont South Carolina
v~. R. Grace Lakeland, FL
Texaco/Canada Calgary, Canada
NASA-STDN Madrid, Spain
Storer Brdctg. Miami, FL
(WGBH)
Susquehanna-WQBA Pennsylvania
Florida Power & Fort Pierce, FL
Light
Susquehanna-WKIS Orlando, FL
Pappas TV - KMPH Visalia, CA
WWL Radio New Orleans, LA
May Broadcasting Omaha, NE
(KFAB)
NASA-STDN Madrid, Spain
NASA-STDN Bermuda
"'sting house Chicago, IL
3roadcasting
Northern Petro- Morris, IL
Chemical
10/76 Elec. Substation
10/74 Energy Control
11/74 Building, Disneyworld
12/74 FM Transmitter Site
01/75 ~ Meterology Tower
75/76 Com. Site & Substations
03/75 Lavnch Umbilical Tower
05/75 3 Tower AM Radio
05/75 Meterology Twr. Atomic Gen.
05/75 Microwave Site
06/75 2 Meterology Towers
06/75 Distribution Line
07/75 Oil Storage Site
07/75 Space Track Site
08/75 4 Tower AM Transmitter
08/75 4 Tower AM Transmitter
08/75 Meterology Tower
07/75 3 Tower AM Station
08/75 300 f t. TV Twr/8000 f t. Mtn
09/75 4 Tower AM Radio
12/75 3 Tower AM Radio
01/76 5 Mi. Transmission Line
01/76 Space Tracking Station
02/76 4 Tower AM Station
01/76 6 Cooling Towers
-3-
Customer
LocAtion
Climetronics
Meterology Res.
NASA
F1 orida Power &
Light
Continental
Electronics
South Carolina
Elec. & Gas Co.
Florida Power
WBBH - TV Ft. Myers, FL
KAYK - FM Provo, Utah
WFPG Radio Atlantic City, GA
Fluor Corp.(PPG) Chlorine Plant, LA
'GM Radio Richmond Hill,
Ontario, Canada
Gulf Power Corp. Pensacola, FL
Phila. Electric Philadelphia, PA
TRC Wethersfield, CT
WLIF Radio Chicago, IL
Robstone Company Miami, FL
Home Cable Jackpot, NV
Conalco Revere Hannible, Ohio
Sandia Labs Albuquerque, NM
TRW - DSSG Adams, MA
KFAB Broadctg. Omaha, NE
E. I. DuPont Dumbarton, SC
Florida Power & Miami, FL
Light
etropolitan Reading, PA
F~li son
Date
Description
03/76 Meterology Tower Site
03/76 Meterology Tower Site
02/76 2 Meterology Towers Sites
05/76 2 Communication Towers
04/76 700 ft. AM Tower
05/76 Generating Plant
05/76 Meterology Tower
05/76 900 f t. TV Tower
07/76 FM Tower on Mountain
07/76 AM RAdio Station
08/76 Large Chemical Plant
09/76 6 Tower AM Station
09/76 4 Umbrella Arrays
11/76 Generator Station
10/76 Meterology Site
11/76 AM Radio Tower
01/77 Dade County Airport
02/77 TV Translator Site
03/77 Elec. Substation
03/77 Communications Site
03/77 Meterology Site
03/77 3 Tower AM Transmitter
05/77 7 Comm. Sites in U.S.
04/77 Meterology Site
06/77 3 Mi. Island Power Plant
(Full Site)
Hauppage, NY
Altadena, CA
Wallops Island, VA
Ft. Lauderdale, FL
Belgrade, Yugoslavia
Eastover, SC
Largo, FL
-4-
Customer
Location
Da t e
Northern Morris, IL 06/77
Petrochemical
MKC Properties ~ Calgary, Alberta, CAN 05/77
Sandia Labs Albuquerque, NM 06/77
Texaco of Canada Edmonton, Alberta, CAN 06/77
Hamana Hospital Louisville, KY 08/77
John Hopkins Laurel, MD 08/77
University
WBBH - TV Ft. Myers, FL 08/77
Conalco Revere Hannibal, Ohio. 08/77
Vail Association Vail, CO 08/77
Sudbrink (WTOW) Philadelphia, PA 08/77
Radio Naples Naples, Italy 08/77
.,unty of San Bernardino, CA 09/77
San Bernardino
Sudbrink (WLIF) Baltimore, MD 09/77
Dayton Power & Dayton, Ohio 09/77
Light
U.S. Erda White Sands, NM 09/77
Sandia Labs Aiken, SC 09/77
Sandia Labs Albuquerque, NM 01/78
Ann Arbor Tran. Ann Arbor, MI 07/78
Ball Brothers 2 USA locations 07/78
Ethyl Corporation Pasadena, TX 06/78
Florida Power & Miami, FL 07/78
Light
Allied-General Barnwell, SC 09/78
Blout Bros. Corp. Westlake, CA 09/78
Stabell Services Ibadan, Nigeria 10/78
Ethyl Corporation Pasadena, TX 10/78
Description
6 Cooling Towers
TV Transmitter on high Mtn.
Meterology Site
3 Oil Storage & Processing
Plants
Hospital Complex
Meterology Tower Site
980 f t. TV Tower
Elec.- Substation
Restaurant & Lift Terminal
FM Broadcast Station
AM Radio Transmitter
300 ft. TV Translator
900 f t. FM Tower
Meterology Tower Site
Transportable Met. Tower
Communications Tower Site
White Sands Test Site
Communication, Dispatch Ctr
Meterology Towers
4 Cooling Towers
System SCADA Center
Processing Plant -
Nuclear Waste
Meterology Sites (2)
Gas Plant
Process Plant
-5-
Customer Location
Date Description
Llanoven S.A. Puerto, Venezuela
Central Louisiana Bunkie, LA
Electric Co.
American Sign & Spokane, WA
Indicator
Blout Brothers Westlake, LA
Euro-Trans- French Gugana
Atlantiq.
Penton-WQSR Sarasota, FL
Cubic Corp. Sardinia, Italy
Jackson Cable TV Jackson, MS
Continental Tel Tucson, AZ
Mobil Oil Beaumont, TX
N.E. Utilities Connecticut
Services
S. Coast Guard Boston, MA
KQIC-FM Durango, CO
City of Atlanta Atlanta, GA
Phelps Dodge Ajo, AZ
Cubic Corp. Sardinia, Italy
KINI - FM Indian Res., SD
WK YT Lexington, KY
Phillips Pet. Bartlesville, OK
WTHI Terra Haute, IN
So. Frvit Distr. Orlando, FL
Digital Systems Stafford, TX
Cloride Southern Mexico
Tehuantepec
KTDS
ream Brdctg. Odessa, TX
11/78 Large Oil Reservoir
11/78 Communications Site
01/79 Computerized Sign
01/79 Meterology Tower Site
03/79 Aries Launch Complex
(2 Sites)
03/79 980 ft. TV Tower
05/79 Radio Control Link
06/79 TY Translator `
10/79 Microwave Tower
11/79 Refinery Area
11/79 Nuclear Gen. Plant
11/79 Microwave Tower/Transmitter
11/79 FM Transmitter on 11,000 ft
Mountain
12/79 Communication Stn., City
09/79 Meterology Tower Site
04/80 Radio Control Center
04/80 FM Transmitter
06/80 FM Transmitter
07/80 Oil Storage Tanks
10/80 FM Transmitter
05/80 Communication Site
02/81 Meterology Site
04/81 Chlorine Plant
10/81 FM Transmitter
04/81 FM Transmitter
-6-
Customer Location
Texas Pipeline Houma, LA
Occidental Oil Grand Junction, CO
Lower CO River Austin, Texas
WRQK - WKOS Greensboro, NC
Lower CO River Austin, Texas
Grasis Tower Co. Tulsa, OK
Canada Atomic Chalk River, Ontario
Cajun Elect. Pwr. New Orleans, LA
Cubic Corporation South Korea
University Stn. Dayton, Ohio
WVUD
Martin Marietta New Orleans, LA
'NASA)
.ederal Express Memphis, TN
Delmarva Power Rivera Beach, MD
Company
Cubic Corporation South Korea
University of Tampa, FL
So. Florida
Texaco Canada Edmonton, Alberta
Rockwell Int'1 Dallas, Texas
Columbia Nitrogen Augusta, GA
Federal Express Colorado Springs, CO
E. I. DuPont Savannah River, SC
Lower CO River Austin, TX
Climatronics Bohemia, NY
^ylix Memphis, TN
RCA America Princeton, NJ
Da t e
06/81
05/81
06/81
08/81
06/81
10/81
09/81
10/81
11/81
11/81
01/82
81/82
01/82
09/82
09/82
10/82
08/82
09/82
10/82
09/82
08/82
08/82
06/82
04/82
Description
Microwave Site
Shale Oil Production Site
Energy Control Center
680 f t. FM Tower
Energy Control Center
Microwave Site
Meterology Site
Energy Control Ctr.
Radio Control Center
FM Transmitter
Large Test Facility
1 Sq. Km of Airport (incl.
3 hangars & 1 Mi . of bldgs.
4 Cooling Towers
Radio Control Center
FM Station
Oil Storage & Processing
Radio Transmitter
Processing Plant
Computer Center
Meterology Towers (7)
Elec. Substation
Meterology Tower
Earth Station
Meterology Tower
-7-
Customer
Location
Da t e
WBAP Radio Fort~Worth, TX 01/82
KFSN-TV Fresno CA 03/82
Cubic Corporation US Navy, SC 09/82
WKZL - FM Winston Salem, NC 11/82
WBBH - TV Fort Myers, FL 02/83
State of Georgia Mental Hospital, GA 02/83
Pappas Telecastg. Visalia, CA 09/83
PPG Industries Lake Charles, LA 09/83
Texaco, Inc. Midland, TX 08/83
Rooney (FEC) Memphis, TN 06/83
Conoco, Inc. Lake Charles, LA 09/83
Steelcraft Memphis, TN 09/83
Federal Express Memphis, TN 07/83
Dept./Transp. Gretna, LA 07/83
Dixie Electric Baton Rouge, LA 08/83
Conoco Lake Charles, LA 05/83
Enviroplan W. Orange, NJ 06/83
TRC Hartford, CT 11/83
Public Radio Greenwell Springs, LA 11/83
Ethyl Corporation Pasadena, TX 12/13
Federal Express Memphis, TN 2/84
NIPSCO Indianapolis, IN 6/84
Delmarva Power Salisbury, MD 6/84
Federal Express Memphis, TN 7/84
Cubic Corporation Bodie Island, NC 3/84
Description
1 AM Radio Tower
TV Tower
Radio Control Center
500 ft. Tower
1000 f t . TV Towe r
Communications Site
TV Tower on 11,000 Mtn.
Chemical Plant
18 Oil Storage Tanker
Large Hangar
Microwave Site
Flight Line structure
Flight Line, Aircraft Docks
Communication Site
Energy Control Center
Microwave Site/Tower
Meterology Tower• 328 ft.
180 ft. Meterology Tower
500 f t. FM Tower
9 Cooling Towers
Airport East Ramp(FEC)
Energy Control Ctr. (Bldg.)
Microwave Site/Tower
FEC Corporate Bldgs.
Radio Control Network Site
~~
-8-
Customer Location
-------- -----'--
Cubic Corporation Thailand
Federal Express Colorado Springs, CO
KDNL St. Louis, MO
WEVY Bonita Springs, FL
Federal Express Memphis, TN
Federal Express Memphis, TN
Tenneco Lafayette, LA
Orange Electric Orlando, FL
WAFB-TV Baton Rouge, LA
Cubic Corp. Thailand
C & C Sales Raytown, MO
Gardner-Zemke Carlsbad, NM
dernreich Brdctg. Cavanal Mtn., OK
Cubic Corporation Okinawa
Gary Englehardt Kutztown, PA
Harrison Int'1 Memphis, TN (FEC)
Columbia Nitrogen Augusta, GA
Gulf State Util. St. Francisville, LA
Gulf State Util. Baton Rouge, LA
Federal Express Memphis, TN
Federal Express Memphis, TN
KPOM-TV Ft. Smith, AR
Phillips Petro. Bartlesville, OK
H. P. Foley Co. Reading, PA
GPU Corporation Reading, PA
Date Description
1/84 Tracking Instrum.Subsys.
10/84 FEC Building
10/84 1151 ft. TV Tower
7/84 680 ft. TV Tower
7/84 FEC Building
8/84 FEC Building
6/84 150 ft. Microwave Tower
8/85 Water Processing Plant
7/84 500 ft. TV Tower
7/84 200 ft. Radar Tower
6/85 Building ~~
Late 85 Atomic Waste Disposal
10/84 166 ft. Tower
1/85 Radar Tower
12/84 Array for House
7/85 FEC Corporate Hq. Buildings
1/85 400 ft. Hot Gas Stack
5/85 Microwave Tower
5/85 Microwave Tower
5/85 3 Hangars - FEC Airport
5/85 Large Building on Airport
4/85 450 ft. Tower
5/85 Cooling Towers
7/85 Computer Center, Public
Utility
7/85 Headquarters & Lab Bldgs.
Customer
Central Louisiana
Electric Company
WFPG - FM
Department of
F,nergy
S. M. Electric
WAVE - FM
WKYT - TV
KQIC - FM
Union Camp
University of
Illinois
Y7AGT - TV
Northern Indiana
Public Service Co.
City of
Lafayette
WKYT - TV
American
University
Computer
Support Service
Federal Express
State of
Louisiana
WPLO
Corps of Engineers
-9-
Location Date
Boyce, LA 4/85
Atlantic City, NJ 6/85
Albuquerque, NM 6/85
Newark, NJ
Sarasota, FL
Maysville, KY
Willmar, MN
Franklin, YA
7/85
7/85
7/85
7/85
7/85
Urbana, IL
Lexington, KY
Highland, IN
Lafayette, LA
Lexington, KY
Washington DC
St. Joseph, MO
Memphis, TN
8/85
Description
200 ft. Grasiss
Tower
Radio Tower
Nuclear Waste
Storage Site
FEC Hangar
FM Tower, 1000 ft.
985 ft. 'fY Tower
Utility Tower
3 Mi. of 69 Kv.
Transmission Line
Radio Tower
10/85 T.V. Station
10/85 Energy Management
Center
10/85 13 Substation
Grounding Systems
10/85 T.Y. Station•Tower
10/85 Media Transmitter
Site
10/85 Asphalt Plant
10/85
Baton Rouge, LA 11/85
Atlanta, GA 12/85
Alburquerque, NM 12/85
Super-Hub Ramp
Expansion
Radio Tower
Radio Tower
Towers/Buildings
Equipment
-l.(~-
Phillips
Petroleum
Brevard County
State of Louisiana
Florida Power
and Light
WPL P - AM
Union Camp
Mill
Federal Express
Complex
Commonwealth
Edison
City of
Colorado Springs
Phillips
Petroleum
City of Lafayette,
Louisiana
CLECO
Building
Northern Indiana
Public Service Co.
Bartlesville, OK 1/86 Storaye Tanks
Titusville, FL 3/86 Communication
Tower
Metairie, LA 5/86 Mississippi River
Bridge Site
Miami, FL 6/86 Communications
Site
t4iami , FL 7/86 6-400f t. Radio
Towers
Eastover, SC 8/$6 Paper Mill
Memphis, TN 8/86 Super-flub
Byron, IL 8/86 Nuclear Plant
Colorado Springs, 8/86 Systems Energy
CO Control
Old Ocean, 7.'X 8/86 Storage Tanks
260' Tower
Lafayette, LA 9/86 Microwave System/&
Energy Management
System ,
Pineville, I.A 9/86 Energy Management '
Center
Ifammdnd, IN 10/86 Microwave Site
r ,, . .,
~G ~ ~ I
~ ~3
LINE VOLTAGE ANOMALIES
AND
OPTIMIZED SOLUTIONS
Roy B. Carpenter, Jr.
APRIL 1983
Report No. LEA-83-1
~~
1~ ~
V
12516 LAKELAND ROAD, SANTA FE SPRINGS, CA 90670
TABLE OF CONTENTS
INTRODUCTION
Background
Scope and Objectives
Definition of Terms or Types of Anomalies
THE LINE VOLTAGE ANOMALY PROBLEM
The Destructive Phenomena
Man-Made Disturbances or Hazards
Disruptive Transients
Disruptive Power Anomalies
Over-Voltage and Under-Voltage Situations
THE POWER LINES PROTECTION REQUIREMENT
For Protection Against Potentially Destructive Anomalies
For Protection Against Potentially Disruptive Anomalies
For Protection Against Primary Power System Anomalies
The Relative Risk Factor
PROTECTION AGAINST DESTRUCTIVE ANOMALIES
Concepts and Considerations
C The Parallel Protector Concept
The Series Hybrid Protector
PROTECTION AGAINST DISRUPTIVE ANOMALIES
Concepts and Considerations
The Hybrid Filter Concept
PROTECTION CONCEPTS FOR DISRUPTIVE VOLTAGE LEVELS
Concepts and Considerations
The Perfect Power Source
SUMMARY OF PROTECTION RECOMMENDATIONS
BIBLIOGRAPHY
l
-i-
LIST OF FIGURES
Figure 1, Line Voltage Anomalies, Page 3.
Figure 2, Sample Surge Voltage as a Function of Distance from
Stroke to Line, Page 6.
Figure 3, Vertical Lightning, Cloud-to-Ground and
Figure 4, Horizontal Lightning, Cloud-to-Cloud, Page 8.
Figure 5, Atmospheric Transients and
Figure 6, Earth Current Transients, Page 9.
Figure 7, Some Earth Current Transients and
Figure 8, Electromagnetic Field Induced Transients, Page 11.
Figure 9, Combined Transient Recording Data (IEEE), Page 12.
Figure 10, The Parallel Protector and
Figure 11, The Series Hybrid Concept, Page 20.
Figure 12, The LEA Surge Eliminator Concept, Page 22.
Figure 13, Surge Eliminator Protective Action, Page 23.
Figure 14, Kleanline Filtering Systems, MB Series and
Figure 15, Kleanline Performance, Page 28.
Figure 16, The Perfect Power Source and
Figure 17, Regulation Concept, Perfect Power Source, Page 32.
LIST OF TABLES
Table 1, The Power Mains Environment, Page 3.
Table 2, Potentially Destructive Power Mains Anomalies, Page 4.
Table 3, Significant Lightning Stroke Characteristics, Page 6.
Table 4, Summary of Risk Factors, Page 18.
Table 5, Comparison of Performance Capabilities, Page 27.
Table 6, Comparison of Regulator Performance, Page 31.
Table 7, Selecting the Protector, Page 33.
Table 8, Regulator Performance Comparison, Page 33.
C
-ii-
INTRODUCTION
Background
The recent progress in electronic systems has brought with it an
increased sensitivity to the operating environment. One aspect
of that environment, the source of power, is also a source of
destructive, disruptive and reliability-deterrent voltage anomalies.
For more than eleven years Lightning Elimination Associates, Inc.
(LEA) has been working in the field of protection systems. One
result has been a natural evolution of protective products that
match the industry requirements as they have evolved. Of course,
tantamount to developing the appropriate product is defining the
requirements governing protector performance. Preparing a compre-
hensive definition of those requirements is as much a part of the
protection task as the design of the protectors.
Scope and Objectives
Voltage anomalies can enter a system via the power line or the data,
control or other electrical connection(s) to the system. This.
paper deals only with the potential power source problems. Other
papers (1)(Z) deal with the other facets of overall systems pro-
tection. Table 1 presents a summary of potential power line
anomalies and their sources.
Power source problems can be classified into two major catagories;
voltage.~~anomalses or complete-loss of power. Complete loss of
power for a significant portion of a cycle~is beyond the scope of
this paper and will be treated in a subsequent paper. This paper
deals with those phenomena, herein termed voltage anomalies, and
in other papers referred to as transients, disturbances and/or
interference phenomena.
These anomalous events can be further classified as either
destructive or disruptive; both are considered in detail herein.
This paper will provide a definition of the source of these
anomalies, derive the resulting specific protection requirements
(define the system power threat), identify the available protective
concepts marketed today, evaluate them against the known require-
ments, and present the best available solution to protect against
each threat or to protect against the total as a single requirement.
Definition of Terms or Types of Anomalies
Anomalies are defined as parameter variations appearing on or
otherwise changing the character of the sine wave from the standard
established by the appropriate national electrical code. This
includes both voltage and frequency deviations.
-1-
Voltage anomalies tend to distort the wave form as illustrated by
Figure 1. Although there are basically three forms of wave form
distortions (surges, noise and RFI), there are other types of
anomalous events that can be destructive and disruptive. These
include over-voltages, under-voltages (brownout) and single phasing.
Where both neutral and a ground are carried through the system
many of these anomalies can appear in common mode and transverse
mode, i.e., between line (hot) and ground and/or between line and
neutral, respectively.
Following is a list of these anomali~
each. The definitions are not meant
define the scope of the phenomena as
An fiver-volts a is a condition where
to we a ove the normal RMS voltage
for a period in excess of one cycle.
es with a short definition of
to be rigorous, but rather to
used within this paper.
the line voltage is elevated
and sustained above that level
An;under-volts a is a reduction in the RMS line voltage to what has
been termed t e "brownout" level and sustained for a period in
excess of one cycle.
A surge (energy surge) is a rapid increase in the flow of total
energy (joules or watt-seconds) to the service entrance, but sus-
tained for periods of :1:ess ~than-:one'hal£:-5cycle;-~ for example, due
toylightning.
Singler:.phasing is the state of a three phase power source when one
p i~ ase is momentarily lost or lost for a period of ,at:~least ::one-•
half cycle somewhere within the public•service system.
Radio. Fz~equen :•znterfeYence `~(12F?,) is a high frequency cyclic
p enomenon superimposed on t e ine frequency by some external
influence or some common user. It is most often manifested in the
form of a damped sinusoidal wave shape as illustrated on Figure 1.
Electromagnetic Interference (EMI°) appears similar to RFI, but is
cause y some externs varying magnetic field mutually coupled
to the facility feeder lines.
•Transients:=are random voltage pulses of relativeiyhigh magnitude,
ut s orbs~uratian, usually less than about 100 microseconds.
i~1oise•c vise's are similar to transients, but of lower magnitude and
uration. They are not considered destructive, but may be disrup-
tive to digital systems.
~Electroma• netic pulse• (EMP) is a single pulse of energy created by
a magnetic pulse suc as t~iat created by ~l:~.ghtniny or a Fnu~lteart
••:burst: The magnitude can vary from insignificant to devastating.
l
-Atmos herscs is an electrical noise phenomenon related to atmospheric
con itions`7sometimes the all-inclusive term "atmospheric electricity"
is used) . It is manifested in the form of ~AQ~.i~~..~ul$~s previously
defined and is caused by distant lightning activity as well as pre
and post lightning atmospheric conditions. It can also be the result
of corona activity from high structures and the impact of the iona-
sphere field on them.
-2-
~'`
FIGURE 1
Line Voltage
Anomalies
Surpet 40 KV
Noise Spike Below
Clamp Levu
----------- RFI
TABLE 1
THE POWER MAINS ENVIRONMENT
POTENTIAL CAUSES
POTENTIAL
ANOMALIES
LIGHTNING
ATMOS-
PHERICS
LOAD
SWITCHING SHOP AND
FIELD
EQUIPMENT
OFFICE
EQUIPMENT
PUBLIC
UTILITY
AUTO-
MOBILES
HIGH
EXPLOSION
OVERVOLTAGE X X y
/
~
UNDERVOLTAGE X V
scrR~s X X X X
SINGLE
PHASING
X
X
~'I X X X X X
EMI X X
INDUCED
TRANSIENTS
X
X
NOISE X X X
EMP X X
-3-
THE LINE VOLTAGE ANOMALY PROBLEM
The Destructive Phenomena
Table 2 subdivides destructive anomalous voltage events into
natural and man-made causes and lists the most common potential
sources. Lightning is a primary source of natural destructive
anomalies. The lightning risk factor is related to the isoker-
aunic number for the area of concern, the character and location
of the facility to be protected (the exposure factor) and the
probability factors related to the lightning stroke itself.
TABLE 2
POTENTIALLY DESTRUCTIVE POWER MAINS ANOMALIES
NATURAL CAUSES MAN-MADE CAUSES
CLOUD-TO- CLOUD-TO- ACCIDENTS
POTENTIAL GROUND CLOUD PUBLIC OTHER OWN AND
ANOMALY LIGHTNING LIGHTNING TORNADOS UTILITY CUSTOMERS PLANT EXPLOSIONS
oVER- X X
VOLTAGES
UNDER- X
X
VOLTAGES
suRGES X X X
TRANSIENTS X X X X X X
EMP X X X
SINGLE X X X
PHASING
The isokeraunic number~;(numbervof lightning; days per year) can vary
from a low of near zero for the artic regions to a high of over 265
for some equatorial regions. While the maximum for the U.S.A. is
100 for central Florida, the average is about 35. Specific values
for a given area can be obtained from a World Meteorological Society
publication ~3~.
The isokeraunic number can be used to estimate the probability of
lightning for a given day (if seasons are disregarded) and the
number of strikes that may be expected to terminate in any given
area for that year. In applying these data two factors must be
-4-
considered in concert. First, the number is an estimator only and
the actual value can vary considerably, and, of more significance
is the fact that it only takes one strike to cause irreparable
damage to electronic systems.
In general, lightning results in three specific, but different,
forms of hazard, direct strikes producing power or energy surges,
induced transients from nearby strikes, and the EMP from the
strike's magnetic field.
A direct strike to any or all phase conductors near or at some
distance from the facility will create a power surge. The
character of this surge is therefore directly related to the
character of the lightning strike, the line it strikes and the
distance to the point of concern. To define the character we
must look at specific cases or parameterize the character relation-
ships. The factors of significance include stroke rise time,
stroke peak current, distance between strokes and the facility or
the resulting line impedance and the grounding resistances at
significant points in between. One significant factor is shown by
Figure 2, where the surge voltage is estimated for an average
lightning strike for various distances from the station of concern.
These numbers must be greatly increased for higher energy strokes.
Some measurements indicate that these voltages could achieve levels
in excess of 100 Kv if the wire insulation would support that
potential without arcing, and if the measurement point was near the
stroke. The higher voltages seem to be the norm rather than the
exception for communications sites, FM and TV transmitters at remote
mountain-top sites.
Table 3 presents a summary of the range of pertinent parameters
which were taken from many sources and represent a compilation of
many works~4-8). The shape of typical lightning stroke current is
such that it rises rapidly to its peak and then tapers off relatively
slowly following a log-normal shaped curve. There are two classes of
lightning strokes; the impulsive stroke and the non-impulsive or hot
stroke. This characteristic determines the damage caused. The
impulsive stroke is the one that ;creates most of the damage to
electronic systems since it embodies a large percentage of high
frequency energy. The .,rate of rise exceeds 10,000 amperes per
microsecond_~and•can achieve rates of over 100,000 amperes per micro-
second. An impulsive stroke usually lasts for no more than 100
microseconds.
The non-impulsive or•hot stroke rises•much.slower. than the impulsive
stroke, as slowly as 500 amperes per microsecond. However, it
usually lasts much longer, extending out to as long as 10 milli-
seconds to the 50 percentile. This type of stroke is responsible
for many fires and explosions.
Induced transients are the second order effects of lightning activity
in or near the area of concern. Their character is related to the
-5-
TABLE 3
SIGNIFICANT LIGHTNING STROKE CHARACTERISTICS /
Charge Range - 2 to 200 Coulombs
Peak Currents - 2,000 to 400,000 Amperes
Rise Time to 90$ - 300 Nanoseconds to
10 Microseconds
Duration to 50$ - 100 Microseconds to
10 Milliseconds
potential Energy at 99$ - 1010 Joules*
*Only a small portion is manifested in a surge,
usually less than 10,000 Joules.
2400
2000
1600
u
a
a~
1200
~ Mile fr
~1 M' Station
a from Sta
ion
• .2 Miles f om Station
-6-
0 1 2 3 4 ~ ~
Figure 2, Sample Surge Voltage as a Function of
Distance from Stroke to Line
lightning discharge and the system character into which the tran-
sient is induced. In general they are high voltage, low energy
disturbances. Estimates of the potential for this phenomenon range
up to 100 Kv (this value is more dependent on the system circuit
parameters than lightning). Installation breakdown levels usually
limit the peak voltages to much lower levels, except on primary
feeders. Public utilities have found that this phenomenon accounts
for most of the lightning faults on lines with a potential of 20 Kv
and lower. Lines as short at 50 feet can pick up a significant
transient, depending on their proximity to the stroke(9). Induced
transients tend to take a shape related to the first differential
of the stroke itself; short, negative and/or positive going high
voltage pulses of lower energy, but often destructive potential.
Induced transients are created by one of three different, but
related phenomena. They are the result of the invisible, but highly
potent electrostatic field found between the charged clouds and the
earth. This field moves and varies in strength with the charged
cloud activity. Cloud-to-earth strikes create the situation shown
in Figure 3; cloud-to-cloud strikes create the situation shown in
Figure 4.
Atmos herically induced transients are created by sudden variations
in t e electrostatic potentials-the atmosphere. Where the clear
air electrostatic field may be 150 volts per meter elevation above
earth, during an electrical storm this field can achieve levels of
up to 30,000 volts per meter of elevation. A lightning discharge
to earth or another cloud will cause this field to collapse, leaving
a bound charge on any conductor within its influence. The resulting
charge seeks ground through any available path, even jumping large
insulators in the way. This creates a voltage pulse that can exceed
100,000 volts. Transients resulting from electrostatic field
changes are propagated over long distances. As one specific, an
average energy, cloud-to-cloud discharge or a strike to earth one
mile away will induce as much as 70 volts per meter of exposed wire
into a thus connected system (see Figure 5).
Earth current induced transients are created by lightning strikes
to t e eart at or near t e acility of concern. With the termina-
tion of a stroke to earth all the charge induced into the earth by
that cloud must move from the point where it was induced to the
point of impact of the stroke (see Figure 6), and thereby neutralize
the charge. As a result of this motion of the induced charge, earth
currents are set up within the earth's crust near thesurface. Any
good conductors buried in the earth within the c arge area will
provide a preferred path for these earth currents and thus be the
recipient of these severe earth currents. The results are induced
transients within the conductor directly related to the earth current
character. Current along the sheath of wires will induce transients
into the inner conductors through mutual induction or these currents
will be superimposed on the conductors without sheaths.
-7-
C'7GURE 3
Vertical Lightning, Cloud -To -Ground ~
-_ - - - - ..fir = ~ - ~-^ - - -- - - - -
i STROKE
CURRENT
~^
_'Y~
+ + l +++ +++ j _- +
- _ + + + + + -
+ GROUND CURRENT GROUND CURRENT
(Distributed) (Distributed)
FIGURE 4
Horizontal Lightning, Cloud - To -Cloud
STROKE CURRENT
+ + + + + + + +
+ +
+ + + + + + + +
~ + + + +
GROUND CURRENT
l
-s-
~/ ''~
I'IGURE 5
Atmospheric Transients
I ~~ ~- ( I I ~ ~ ~ I I
I I
ELECTROSTATIC ---I NEARBY I ~ I
STRIKE I ~. I I
FIELD I I I ~ I I I '
o~~O~D o~0 p0~~ ~ ~
SUSPENDED •
INTER-PLANT • POWER LINE
DATA LINES
• Will experience induced transients
--
%~ FIGURE 6
,..
-~' Earth Current Transients
~i ~~ rG~^
• +
+ + + ++ oo~t7p0~ O~
+ + + + + + ~°o^ O~~ +
EARTH CURRENT ~_ BURIED + +
TRANSIENTS + + + LINES • + /
-9-
Figure 7 illustrates two other forms of earth current transient
effects. The results on the connected system are the same regard-
less of the cause.
Electromagnetic field induced transients are also created by
lig tning disc arges. For this phenomenon the lightning flash
channel acts as a large vertical radiator or antenna. The large,
rapid flow of current down the ionized lightning flash channel sets
up a rapidly changing electromagnetic field propagating out from
the stroke channel in much the same fashion as AM broadcasting
stations and is the cause of static in a radio receiver, reflected
waves in the 'transmitters and transients in nearby conductors as
shown by Figure 8. Generally, cloud-to-cloud strokes produce pre-
dominantly horizontally polarized waves while the cloud-to-earth
strokes produce vertically polarized waves. The di/dt's often
exceed 100,000 amperes per microsecond.
Tornados create a
indT used transients
generator. This
within the eye of
rotates the induc
of rotation of th
to electronic svs
cyclic var
are of a
phenomenon
the twiste
ed voltage
e twister.
terns if the
tmospheric
a poor s
a charge
motion.
with and
entials c
near an a
field; the
awtooth
separation
As the twister
at the frequency
an be damaging
rea of concern.
To protect against all of these destructive forms of induced
transients, regardless of their cause, the protective equipment
must be designed to satisfy the worst case situation, i.e., at
least 99 out of 100 possible events. The protective requirements
include the following:
Transient Energy - 500 Joules
Transient Peak Current - 20,000 Amperes
Transient Peak Voltage - 6,000 Volts
Transient Rise Time - 50 Nanoseconds
IEE Standard 587-1980 presents a summary of findings from several
sources. Figure 9 presents a composite of pertinent transient data
as recorded by the different investigators.
Man-Made Disturbances or Hazards
Man-made disturbances come from the electrical system's environment
as created by man. Again, these disturbances can be the result of
a directly injected phenomenon or an externally induced phenomenon.
It is futile to attempt to define all the potential causes, but the
following identifies and deals with some of the more significant
possibilities. Man-made disturbances may be subdivided into those
caused by electromagnetic or electrostatic fields and those caused
by some form of "accident".
iation in the a
shape similar to
is the result of
r and its rotary
rises and falls
The induced pot
twister passes
-10-
FIGURE 7
Some Earth Current Transients
- -
COUPLING VIA:
(1) IR DROPS
(2) MAGNETIC FIELD
-_~
~~~~ ~
~•^\ `
1 ~/ V
~i
~ ~ - ~/
EARTH CURRENTS /
FIGURE 8
Electromagnetic Field Induced Transients
...
~.,,~ r-~-..-~
ELECTROMAGNETIC
FIELD
(EMP)
10~.._---- 1
t=
~~,
.,
''
,.
;.:.:-.
-ii-
FIGURE 9
Combined Transient Recording Data (IEEE
105
104 RURAL
OC 103 ~
} 102- _
D:
a 10~
w 1
~ 10•t
N
10.2
10.3
0.2 0.5 1 2 5
SURGE CREST KV
10 20
-12-
HIGH
EXPOSURE
MEDIUM
EXPOSURE
SPARKOVER OF
CLEARANCES
LOW
EXPOSURE
a
Man-made electromagnetic field transients are usually created by
poor installation practices or inflexibility in the plant layout.
For example, the power lines for large motors and power lines for
sensitive electronics are laid side-by-side in the same cable tray
or raceway.
During the planning stages for a plant, it should be understood that
power lines carrying any large loads will also carry and/or create
transients on those lines as well as lines nearby. Electric motors
with poor commutators will radiate transients into nearby lines and
cause malfunctions in any electronic equipment sharing the common
source of power; SCR switches, switching power supplies and the like
are common offenders.
Directly injected hazards are usually the result of Murphy's Law at
work. The possibilities are as diverse as the industry itself.
Some common examples, that have happened include:
(1) High voltage wires dropping onto the lower voltage lines,
arcing over them, or striking them in high winds or accidents.
(2) Failure of insulation or isolation devices which inject a
high voltage onto the lines. This happened three times in
one year at three similar facilities separated by thousands
of miles. In all three cases a related computer was destroyed.
The electromagnetic pulse (EMP) resulting from a large atmospheric
explosion, usually nuclear, will also create this phenomenon. The
character of the EMP is usually considered similar to lightning,
but with much faster rise times (nanoseconds) and much shorter
duration (only a few microseconds). The energy induced into a
facility can be very high if it is located near the center of the
explosion, in excess of 100,000 joules.
Disruptive Transients
A disruptive transient is some form of voltage anomaly of less than
a half cycle duration that is superimposed on the power line (mains)
at a potential below the destructive level of the equipment it feeds,
yet high enough to impair proper operation or significantly reduce
the data or equipment reliability (mean time before failure).
The causes of disruptive transients are similar to those classified
as destructive, but at lower voltage levels. Specifically, they
include atmospherically induced transients, earth current induced
transients, EMP induced transients and all of the man-made anomalies.
In addition, disruptive transients can be caused by radio frequency
interference (RFI) which is created by:
(1) Cross coupling between cables in the same cable tray or raceway,
(2) Nearby radio, AM, FM or TV stations, radar, or
-13-
(3) Other types of equipment, such as motors or welders, any vary-
ing high current load using the same feeder, or radiated energy
from nearby equipment which is manifested in the form of elect-
romagnetic or electrostatic fields.
The potentials and forms of disruptive transients are related to
the lines on which they are induced. Some sample forms are shown by
Figure 1. Refer back to the definitions for a description. The
parameters of concern are:
(1) Peak noise or transient voltage which is found to vary from
insignificant to values approaching the destruct level, i.e.,
nearly 400 volts peak-to-peak on a 120 volt RMS line and over
800 volts peak-to-peak on higher voltage lines. All are
usually of very short duration, a few microseconds.
(2) Radio frequency interference which usually takes the form of
a damped sine wave with peak voltages as in (1) above for the
first cycle and frequencies extending from harmonics of the
primary power source to the very high frequency band.
Disruptive Power Anomalies
There are several forms of disruptive power anomalies, some of which
are:
A short-time loss of one or more phases is the most common fault.
These incidents usually last from one to ten cycles, often with
repeated on-off switching transients, and vary significantly in
frequency of occurrence with the reliability of the utility servicing
the area, and more significantly, with the isokeraunic number for the
area.
Extended outages are unusual for developed countries, but do happen,
usually because "Murphy" got into the act (a drunk hits a power pole)
or human errors of one sort or another. Statistics on duration of
outages are about as follows:
90$ less than ten minutes
95$ less than 30 minutes
99~ less than one hour
Worst case has been several days
Over-Voltage and Under-Voltage Situations
These conditions are the result of public utility action and/or
customer overloads.
Over voltates are a much less common problem and almost exclusively
t e result of poor control by the utility. The statistics indicate
that over voltages above 110 of the rated feeder voltage and lasting
-14-
over one-half cycle are almost non-existent in well developed
countries. The probability is so low as to eliminate its considera-
tion except possibly in some "third world" countries. However,
protection against this phenomenon can be accomplished at little
expense and may be worth it.
Under volta es or brownouts are a very real concern in just about
any part of t e wor Line voltage drops down to about 85~ of the
normal rating are becoming an all too common occurrence. and are the
result of customer overloads and/or the utility deliberately reducing
the driving voltage to prevent overloading the generators.
To properly design for extended line voltage variations the designers
should plan on variations of between plus ten percent and minus
twenty-five percent around the norm, at least at the secondary. level.
A remote location where the consumer is at the end of a distribution
line or on poorly controlled rural power is the primary area where
wide variations in line voltage can be expected.
-15-
THE POWER LINES PROTECTION REQUIREMENT
The protection requirements for systems operating off common public
utility power lines can be defined by the systems` protection re-
quirements and the related environmental threat. This mandates a
division of these requirements into the previous classifications and
results in the following:
(1) For protection against potentially destructive anoT[ialies -
(a) Surge energy withstand capability of at least 10,000
joules per phase*
(b) Surge current withstand 160,000 amperes peak*
(c) Peak voltage withstand up to 45,000 volts at service
entrance and/or 6,000 volts at wall socket
(d) Reaction time less than 50 nanoseconds
(e) Fail-safe protection against extended over voltage
*Independent of wave shape which is related to the
surge energy withstand, i.e., any shape containing
that energy level.
These requirements are for such analogue facilities as radio ~.
stations, UPS isolated conputers, motors and other more
rugged electrical gear. Subdivisions within this catagory are
possible if related to the specific point of concern as
recommended by the IEEE (lo),
(2) For protection against potentially disruptive anomalies -
Protection against destructive anomalies, above, is required,
plus:
(f) Low energy transient voltage peaking just under the
protection level, but well above the disrupt level. This
varies with equipment, but may be taken as any value from
about 50 volts peak to 400 volts peak-to-peak for a 120
volt RMS line or as much as 1,000 volts or more for the
higher line voltages.
(g) Radio frequency filtering for a band of frequencies
starting at 1 KHz and extending to 100 MHz. If protection
is provided against all of the other potential events,
attenuation in excess of 40 db is usually not required.
-16-
(3) For protection against primary power system anomalies -
Protection against items (1) and (2) above plus:
(h) Voltage regulation to about ±5~ with input variations of
from +10~ to -25$; better re ulation is not required.
The fact that closer regulation can a ac ieved wit in
bounds does not make it a requirement or even desirable.
Regulation response time requirements are related to the
protective system filter characteristics, that is, the
filtering capability must eliminate variations the
regulator does not respond to. For example, for a 60 Hz
system, if the regulator responds to I/4 cycle or about
4 Ms the filter should be capable of filtering out all
transients of lesser duration.
(i) Protection against power outages or single phasing (i.e.,
the loss of one or more phases of a three phase power
source for a significant period). This protection must
take the form of a power source substitute or must protect
against the impact of power loss by performing an orderly
shutdown (orderly shutdown is defined as providing enough
warning time to preserve data, status and/or essential
functions). For many situations audible warning and
complete shutdown within one to three minutes will satisfy
most requirements. At this point the individual customer
must define his specific requirements. Where complete
loss of power cannot be tolerated for even very short
periods or low probabilities, an uninterruptible power
source is required. Only ten minutes of uninterrupted
power is sufficient for over 90$ of the situations.
The Relative Risk Factor
The foregoing data is a compilation of data derived from many
sources relative to these phenomena within the context. For
example, given that lightning exists, what is a reasonable risk
range for the pertinent perameters? Now, it is also necessary to
relate the individual risk phenomenon to each other. To that end
IBM sponsored a landmark study that provides the only well docu-
mented details as to this relationship for computer installations.
In using the data it should be recognized that the risk relation-
ships are basically for urban areas and not necessarily representa-
tive of the experiences at mountain-top sites, rural areas or third
world countries. Table 4 presents a summary of the risk factors
by catagory as IBM identified them.
To deal with the differences between the urban area situation and
that related with the less populated areas, consider the one factor
illustrated by Figure 9. Note that as the data points are moved
-17-
to more rural areas the risk of exposure to higher levels of
voltage transients, surge currents, etc. increases significantly.
This is because there are less subscribers to share the problems.
TABLE 4
Anomaly Percentage Number per Day
Over-voltages, including surges 2$ (6 per year)
Under-voltages 25$ 1
Outages, including single phasing 1~ (3 per year)
Common mode transients* 27~ 1
Transverse mode transients* 45~ 2
*49~ of these were the damped RFI waveform
These data further indicate that for the average urban U.S.A.
installation a disturbing voltage anomaly of some form may be
expect d on the average of more than four times per day for
sensitive electronic systems. In summary, there will be
disturbances; you must be prepared.
-18-
..
PROTECTION AGAINST DESTRUCTIVE ANOMALIES
Concepts and Considerations
There are numerous and diverse devices marketed as surge protec-
tors. Manufacturers make similar performance claims, yet the units
vary in cost, physical size and components. Their performance is
seldom related to the threat and different performance parameters
are often used to define their capability. It is therefore necessary
to evaluate all such devices against some fixed standard that is
representative of the actual threat. If compromises are made below
this standard the related risk should be specifically defined so the
buyer is properly informed.
Of equal importance to performance parameters is the method of
employment of the device within the protected system circuitry. To
that end, there are two ways of implementing the protective device
within the circuit. The protector. can be installed in parallel with
the device to be protected as illustrated by Figure 10 or it can be
installed in series with the incoming power between the source and
the system to be protected as illustrated by Figure 11.
The Parallel Protector Concept
All of the conventional surge protectors with the possible exception
of isolation transformers and LC filters are designed to be wired in
parallel with the load they protect.
Note: Isolation transformers and LC filters provide no lightning
or surge protection and, when exposed to these anomalies,
are subject to destruction themselves.
An analysis of the functional circuit diagram of Figure 10 reveals
deficiencies in the performance effectiveness of any parallel pro-
tector, device or assembly, as follows:
(1) Because it forms a parallel circuit with the protected system
the "protected" must share the surge with the protector. Of
course, the protector is supposed to become a very low impedance
path in comparison to the protected equipment -- at just the
right time. Yet it must not compromise the system performance
or waste power. Two other factors further mitigate the per-
formance of the parallel protector. The clamping voltage must
usually be set high (several times the normal operating voltage)
to prevent inadvertant operation or excessive parasitic power
loss and the parallel impedance cannot be too low or it will be
subject to the high energy from the driving power source. The
latter problem is accentuated by low impedance sources. Also,
the clamping ratio is often too high for very sensitive
electronics. Ratios in the order of from five to twenty to one
are not uncommon for these devices. This means that peak volt-
ages of up to 4 Kv or more can be registered on a 115 V RMS line
under high surge current conditions:
-19-
. ~ .
FIGURE 10
The Parallel Protector
Line
Lc
Is ~ Surge Curre~~~
Lc s Inductance of Connections
to line.
Lg a Inductance of Ground Connection.
FIGURE 11
~~
1
The Series Hybrid Concept
Service Surge
Entrance Eliminator
Lc EL __
Is load E~
-~-- --
Es 1s Reference
Point
-' -- Is =Surge Path
-20-
,i
' Parallel '
--- -
(a) The clamping voltage. is the peak voltage at which the
(~ protector starts to limit the line voltage.
{b) The clam ing ratio is the ratio of the line voltage
wring surge pe c3-_.current ..vs the- initial clamping
.voltage.
(2) The wiring that integrates the parallel protector into the
circuit becomes a series impedance to the flow of the fast
rising surge currents (also shown by Figure 10). Rising
current rates in the order of 100,000 amperes per microsecond
are not uncommon. Under these conditions each meter of length
of connecting wire may be considered about 1'~ microhenries of
inductance. The result is a significant series impedance in
the circuit and the voltage developed across these connections
adds to the voltage across the "protected" system.
In summary, the parallel protector concept is considered a compromise.
The only advantage it has is ease of installation. Some of the
devices in this class are. low cost, others (assemblies) are very
expensive; none satisfy the total protection requirements.
RThe Series Hybrid P~rotectbr
The series hybrid Surge Eliminator (SE) developed by LEA, Inc.
(patent pending) eliminates the series impedance influence of the
( connecting wires by separating the surge current path from the control
voltage sensor as illustrated by Figure 12. The SE solves the high
clamping ratio problem by using the series impedance to dissipate
any over-voltage and separate it from the load. It solves the high
clamping voltage problem by separating the unstable, power wasting
components from the on-line control circuit.
To illustrate Surge Eliminator performance consider the situation
depicted by Figure 13, which presents a badly distorted sine wave
for a 120 volt RMS hot-to-neutral situation where several forms of
destructive voltage anomalies are shown. The equipment destruct
level is assumed to be above the ±200 volts peak; normal peaks are
about 166 volts. The surge protector must prevent the voltage from
rising significantly above that level. To accomplish this the SE
functions as followsr
(1) The voltage controller assembly constantly monitors the output
voltage with no significant parasitic loss.
(2) When the voltage rises above the clamp voltage, usually set at
1.2 times the normal peak voltage, the voltage controller acts
as a constant voltage device holding the voltage at the
selected clamp level.
(3) If the anomaly is more than a small transient the High Energy
Dissipation Assembly is activated dissipating only the surge
._ energy like a clipper.
-21-
r ~
Zlri
FIGURE 12
( IN
Series OUT
~ Surge Impedance I
( Switch
~ I
I High I
~ Energy I
~ Switch ~
I Voltage
I Controller ~
High I
Energy I
I Dissipator I
I
I
~------ - ----J
Protected
Equipment
t__T_J
Common Point
Grounding _ Local Ground
Matches Input Impedance
Power
Surge Fuse Characteristic
Fully Probability <1/10 yrs.
Protected w/o
Interruption
Time
LEA Surge Eliminator Concept
C
C
~.
-22-
~ r ~
+200
+166
0
n-
structive
-166
'-200
A, Before Protection
~ Note Tight Clamp +Clamp Level
+16 6 --~ - - - - - - - - -- - -~--~- - - -- -
0 ~-- - - -- - - -L ~ - - - ~-- ~--- -- - -~ ~- - - - - --~ ~- ~
-166------ ------`-'' --- ---------
-200 -
-Clamp Level
B, After Protection
Figure 13,, Surge Eliminator Protective Action
t
-23-
..
`1~
Destructive Surges
PROTECTION AGAINST DISRUPTIVE ANOMALIES
Concepts and Considerations
Disruptive transients, as previously defined, are the largest
segment of hazards presented by the power mains. The
concept must protect against destructive anomalies as welleaslthe
non-destructive but functionally disruptive anomalies. The
for digital equipment must provide, in addition to li htnin protector
tion, both RFI filtering and noise rejection such that the g Protec-
voltage from either phenomenon does not exceed about f20$ ofethe
normal line voltage around any point in the sine wave.
Protectors marketed for this purpose are limited to some form of
series type protector. No parallel device could significantly
influence all of the stated problems
unsubstantiated claims to the contrar yet some suppliers make
protector for disruptive anomalies includehRFlofilters-LCpnetworks,
isolation and so-called super-isolation transformers, and multi-
stage series hybrid systems.
In reviewing these potentially protective concepts, the parallel
types such as encapsulated MOV's, gas tubes and zeners or transzorbs,
etc., may be dismissed as obviously not effective, even though their
packaging does not always make this clear. Traditionally, some form
of LC filter is still used to deal with these anomalies. In review-
ing contemporary RFI filter/isolation transformer concepts we finA•
(1) The RFI filters provide
to over 50 MHz, but no
(2)
only RFI filtering from about 150 KHz
significant lightning protection.
The isolation transformers provide filtering from about 1 KHz
to 1.5 MHz, but again, no significant lightning protection.
Both of these filters provide a measure of noise su
the filter characteristic and/or asa result of the shieldingnconcept.
Both are usually effective only against transverse mode anomalies.
Common mode anomalies are often either neglected or dealt with in
some limited or unorthodox manner, such as not carrying the ground
wire through the filter uninterrupted. Some of the super-isolation
transformers do provide both modes of filterin but the u
frequency is limited to about 1.5 MHz g' PPer
problems at 10 MHz, yet there are significant
In summary, none of the RFI filters, isolation transformers or
super-isolation transformers presently available can satisfy all the
requirements for protection against both destructive and disruptive
line voltage transients. LEA has therefore developed the multistage
series hybrid protector called the Kleanline Electronic Filtering
System to satisfy this need.
-25-
,,
The Hybrid Filter Concept
The LEA Kleanline series hybrid concept is based on the premise
that a protector must be designed to deal with all the
disruptive voltage anomalies in common and transverse modesnincludi
both broad band filtering and surge/over-volta e
Fi ure 14 ng
g illustrates-the functional logic used inrthecKleanline
Filter to accomplish protection against all of the known hazards of
a transitory nature as well as sustained over-voltages.
Kleanline Electronic Filtering Systems
they clean the power mains of all unwantedfelectrical anomaliesrfrom
lightning related power surges to noise
tudes and less than a microsecond durationlinsbothdcommonlandatrans-
verse modes. Further, these units satisfy the CSA, UL and VDE
specifications. This unusually comprehensive concept has been
proven by many major firms in the data processor field as the only
totally effective protector.
LEA Kleanline Filters are designed around a four-stage, series
hybrid concept shown on Figure 14. The first section is a Surge
Eliminator which eliminates any over-voltages or power surges in
excess of a voltage equal to 120 percent of the normal peak line
voltage as previously described.
The two series filters are stagger-tuned to provide RFI, EMI and EMP
filtering across a band of frequencies ranging from 1 KHz to well
over 200 MHz, providing from 35 to 40 db of filtering in both common ~
and transverse modes without introducing more than about 10 micro-
amperes of leakage current to ground (earth) for the lu
Refer to Figure 15 for a typical band rejection characteristicnits.
The second stage removes any high voltage transients that may pass
through the first stage. This voltage limiter reacts within 5
nanoseconds and will remove any form of over-voltage above clamp
voltage.
A final stage is included to remove the "leftovers", the low voltage
noise spikes and RFI in both common and transverse modes. This
function is intended to follow the sine wave and strip it at any
point in the phase relationship at about ±20$ of peak voltage. As a
result no significant anomaly can pass through the Kleanline Fitt-P,-_
In summary, the Kleanline Electronic Filtering
hensive system of active and passive filtering
significant voltage anomalies in an economical
It then clips off any overshoot above the clamp
provides a reasonably clean sine wave output.
System is a compre-
which removes the
and effective manner.
level and, finally,
-26-
( As a matter of academic interest, Table 5
pres
t
performance capabilities of en
s a comparison of
contem orar
r
provide protection against
E destructive and
disru
ti
a
ven a cursory comparison a
form of s
i p
ve
anomalies.
t the most basic levels
s
h
er
es, multistaged
all the requirements is com hybrid protector is required
to
satisfy
l
p
ete protection is desired.
TABLE 5
COMPARISON OF PERFORMANCE CAPABILITIES
(2)
Protector Makers Surge
Protection
~'I Noise Rejection
RFI Filters Corcom, NONE
HF
Aerovox, Filter Related
NONE
C. D. HF Filter Related
NONE
HF Filter Related
Isolation & Topaz,
Super- Deltec NONE LF(1) Filter Related
,
Isolation Solar NONE LF(1) Filter Related
NONE
Transformers LF(1) Filter Related
Kleanline 'LEA, Inc. Total HF
Absolute Noise
Protection and Stripping
LF
Notes - (1) More than required to achieve some noise rejection.
(2) Parallel protectors such as Transtector, GE, MOV's, TII and
other gas tubes are not included as they include no RFI or
noise filtering.
(3) HF is high frequency RFI filtering, LF is low frequency
RFI.filtering.
-27-
.a
IN
L O~
N a
G 4-
To
Power
line
FIGURE 14
Kleanline Filtering Systems , M B Series
Singie Phae (1.16 Ampere)
iur OUT
=use Surge Hph Low Trensverte Line
Protector FrF11te~ Frequency Mode
Filter Stripper Neutrs~
Common Noise Stripper
Multiphase
Surge Low High
Fuse Frequency Frequency
Fiber Filter
High
Oissipa~r Con ~ Stripper
l
To neutral or ground terminals on unit
KieanNne Performance
FIGURE 15
A M~
Ground
To
Protected
Equipment
~o
eo
~o
so
m
to
~~
~~i
-2g
» r ~
PROTECTION CONCEPTS FOR DISRUPTIVE VOLTAGE LEVELS
Concepts and Considerations
A disruptive voltage level has been defined as including sustained
over-voltages, under-voltages (brownouts), loss of power and the
related single phasing phenomenon. The concepts emplo ed to
against these. voltage anomalies are very limited, including varioust
types of transformer technology, various forms of switching tech-
nology and some type of on-site generator or UPS. Each of these
concepts have some advantages and some disadvantages; none of them
alone satisfies all of the protective requirements (see Requirements
De- nition).
The various transformer concepts include;
(1) The saturable reactor which is designed to operate under normal
voltage at saturation. Over-voltages tend to over saturate the
reactor and produce no appreciable increase in voltage at the
secondary. Under-voltages are below saturation and therefore
result in some effective increase in the transformer output.
The operating range is obviously very limited, the waveform
distortion is often intolerable, and they are very load
sensitive.
(2) The ferroresonant transformer or line conditioner is the most
popular solution in use today -- basically because of lack of
competition in the past. As the name implies, this device is
a resonant LC network, static generator or magnetic flywheel
device. Through use of a combination of L and C in various
resonant and/or buck-boost winding configurations they seek to
stabilize the output voltage at some predetermined voltage.
Over a limited range of input voltages and load ranges they
are reasonably effective, but the user must be able to tolerate
the resulting high series dynamic impedance, limited regulation
range, inrush current limiting and high parasitic power loss
(poor efficiency). On the positive side the do
inexpensive regulation at the lower Kva ratings and~vife
significantly under rated with respect to load current (less
than 50~), they provide a significant amount of single cycle
fill-in. They offer no lightning protection and only low
frequency RFI filtering (1 KHz to 1.5 MHz) in transverse mode
only.
(3) The motor driven or manuall o erated to switcher/transformer
is a good alternative where slow reaction tame and switching
transients can be tolerated. These devices use multi-ta
transformers that are switched to regulate the output voltage.
The motor driver options are expensive and no longer a cost-
effective option. These devices offer no lightning protection
and very little low frequency filtering. The usual configura-
tion creates significant transients during the switching
operation.
-29-
.i
~ T
(4) The motor driven or manuall ad'ustable transformer (variable
transformer, Variac) is very similar in concept to the tap
switcher (3) above, except the taps are Closer together (one
per turn). These are a significant improvement over the tap
switcher, but display the same disadvantages to a lesser degree.
For example, the switching transients are normally much lower.
These units do have a wide range of control, but little filter-
ing, and the added costs render them non-competitive except for
special applications.
(5) Electronicall switched transformers include two basic types,
zero voltage crossover switching and zero current crossover
switching. Of the two, zero voltage switching is the more
popular because of the lower cost. Both concepts permit fast
switching, as much as once every half-cycle if necessary. Both
can be efficient, up to 96~, both can be produced with as much
isolation as the so-called super-isolation transformers, and
both can be produced with any number of options. On the nega-
tive side, bath cost more for low Kva ratings and both suffer
reliability problems because of the complex electronic control
requirements.
The zero voltage switcher senses the peak voltage. When it
strays beyond the prescribed boundries it then switches to the
next tap, up or down at the next zero crossover voltage point.
Often, a significant transient is generated, and further, two
switches can be in the "on" state at the same time and switch-
ing jitter can occur when the line voltage tends to hover at a
switching point. The zero current switcher usually senses the
peak. However, they switch at the next zero current crossover
point. To do this they must sense current flow as well as the
voltage which adds to the complexity.
The Perfect Power Source (Patent Applied For)
The perfect power source must regulate, protect and filter. If only
part of these functions are satisfied the unit is incomplete and
only partially effective.
The LEA Perfect Power Source (PPS) provides all of the required
functions in one package as shown by Figure 16 including protection,
broadband filtering and regulation. The system it services is pro-
tected against any anomaly short of complete loss of power, much less
than one percent of the possible hazards.
The PPS uses the inherent filtering capability of the Kleanline
Electronic Filter as the basis for the PPS design and simple, reli-
able relay switching to change the taps. The two problems formerly
associated with relay switching are overcome as follows:
(1) The slow switching problem and potential loss of a portion of
the sine wave was overcome by using a close-before-open concept.
-30-
.~
r •
(2) The potential switching transient and short circuit current
resulting from two taps closed for an instant
millisecond) has been eliminated by the filter (components
as illustrated by Figure 17.
The resulting LEA PPS regulates the output voltage to within 5$ of
the nominal voltage with input variations of from about minus 25$
to plus about 10$. Rapid tap changing is eliminated by switching
only when there is at least a 1~ change in output voltage.
No significant transients, noise or RFI are generated within the
PPS or passed through it. No portion of a sine wave is lost or
distorted. No harmonic distortion is introduced and the dynamic
impedance is not significant.
Table 6 presents a comparison of pertinent performance character-
istics for the ferroresonant regulators and the LEA Perfect Power
Source. The only requirements the PPS does not satisfy are those
related to loss of power on one or all phases. To overcome the
single phasing, warning and automatic shutdown options are offered.
Compare the PPS to ferroresonant devices that claim to provide
single phase or loss of cycle fill-in, but offer only some small
measure of capability by derating the re ulator by as much as 50$.
T~~ 6, COA4PARISON OF REGULATOR PERFORMANCE
CONSIDERATIONS
FERRORESONANT
PPS (1)
Load Sensitivity
Regulation Range
Dynamic Impedance
Noise Filtering
Waveform Distortion
Inrush Current Impact
Carry-Through Capability
Cost Factor
Harmonic Distortion
Efficiency
Lightning Protection
Audible Noise
Over-voltage Protection
Very Sensitive
+10$ -20$ maximum(4)
Very High
About 1 Khz to 1.5 Mhz
High (4)
Field may collapse, will
create transients
If oversized about 100$(3)
.See Figure 17
High
50 to 85$(2)
NONE
High
NONE
Notes: (1) The LEA Perfect Power Source
(2) Directly related to percent load vs rating
(3) Inversely related to percent load
(4) Load Sensitive
Insensitive
+10$ -25~
Low
1 Kc to 200 Mhz
NONE
NONE
Less than ~t cycle
See Figure 17
NONE
90 to 96~
Unlimited
Insignificant
Protected
-31-
~"
FIGURE 16
The Perfect Power Source
Lightning Common &
Protection Transverse
Filtering
Input:
80 to 135V RMS
voltage
Control
Output:
115V t 5V RMS
FIGURE 17, REGULATION CONCEPT, PERFECT POWER SOURCE
i~
-32-
l
s a s
' SUMMARY OF PROTECTION RECOMMENDATIONS
We have found that there are three levels of _
ments, and this mandates three levels of protectorsttonsatisfye
/ these requirements:
(1) For protection against destructive anomalies use the
Surge Eliminator (SE),
(2) To add protection against disruptive transients use the
Kleanline Electronic Filtering Systems (MB), .
(3) To add voltage regulation use the Perfect Power Source (PPS).
Relating this to the incident risk established by Table 4, Table 7
below identifies the scope of protection provided.
TABLE 7
Selecting The Protector
Anomaly SE MB PPS
Overvoltage ALL ALL ALL
Undervoltage None None ALL
Transients Destructive ALL ALL
Outages None None None
Percentage Eliminated 29°~ 78% 99%+
Comparing the Perfect Power Source to competitive protector/
regulators, Table 8 below establishes the advantage of the PPS over
the rest of the marketplace.
TABLE 8
Regulator Performance
Comparison
Type
Ferroregulator
Isolation Transformer
Competitive Switchers
PPS
Percentage Protection Against:
Destructive Disruptive
None 10°~
None 27%
None 12y0
ALL 99°~
*One form of disruptive anomaly can only be eliminated by
some form of constant voltage source, such as a generator
plus a UPS. One or the other will only eliminate some
portion of the remaining one percent.
.. _~~
f .~ s
BIBLIOGRAPHY
(1) Lightning Strike Elimination, The Story of Dissipation
Array Systems, Roy B. Carpenter, Jr., September 1979,
Report No. LEA-79-1
(2) Protection Requirements and Concepts for Data and Control
Lines, Roy B. Carpenter, Jr., November 1980,
Report No, LEA-80-8
(3) World Distribution of Thunderstorm Days, World Meteorolo ical
Organization, Secretariat, Geneva, Switzerland, 1953 g
(4) Atmospheric Electricity, A. Chalmers, Pergamon press, 1967
(5) Lightning Protection, R. H. Golde, E. Arnold Publishers, 1973
(6) Lightning, M. A, Uman, McGraw-Hill, 1969
(7) The Lightning Book, P. E. Viemeister, The MIT Press, 1972
(8) Lightning Protection, J. L. Marshall, Wiley & Sons, 1973
(9) Characterization of the Electrical Environment, D. W. Bodle,
et al, University of Toronto Press, 1976
(10) IEEE Guide for Surge Voltages in Low-Voltage AC Power Circuits
IEEE Std. 587-1980, Sponsored by Surge Protective Devices
Committee of the IEEE Power Engineering Society
-34-
..
~. ..
... Part I-on
the power lines
Dealing with lightning...
he progress in electronic systems
Tdeaign has brought with it an
increased sensitivity to the operat-
ing environment and to the interface
rnnnections. These interfaces bring with
them both the desirable and the unde-
sirable. The interface of concern in this
article ie power lines.
The power lines bring in the motivat-
ing power for the cable system. They
also bring destructive and disruptive
electrical transients, herein termed
anomalous events.
Destructive anomalies are electrical
events superimposed on the normal
line wltage that cause it to be elevated
above the safe level or operating range
of the equipment it feeds, regardless of
the character. This is normally taken
at 120 percent of the normal peak
wltage. Aa an example, it would be
between 200 and 250 volts for a
120-w1t RMS line.
Disruptive anomalies are electrical
events superimposed on the normal
line wltage that create a situation
within the unit fed that causes it to
momentari ly malfunction. This momen-
tarymalfunction cauBes erroneous oom-
mande, creates faulty data or "locks
up" a system. This can bean annoyance
and sometimes costly in loot time. but
does not cause damage.
This article is an attempt to elimi-
nate some confusion on lightning pro-
tection by deCning known hazards and
comparing the performance of con-
temporary protectors with the hazards.
thus providing a reliable decision tool.
The data used to define the hazards has
been taken from 'a wide variety of
publications on the subject.
One of the problems related to light-
ning protection ie the jargon used and
the way it is used.'ib eliminate misun-
derstanding, it is necessary to define
beaic terms encountered in discussing
lightning.
An over voltage occurs when line
voltage ie elevated to well above the
normal RMS voltage and sustained
above that level for a period in ezoA~e
of one cycle (over plus 15 percent).
An under voltage occurs when the
1tMS line wltage drops to what ie
termed the "brownout" level and re-
By Roy B. Carpenter,
Lightning Eliminators & Conaullanti
mains at that level for a period in
excess of one cycle (over minus 20
percent).
An energy surge is a rapid increase
in the flow of total energy (joules or
Watt-seconds) to the service entrance
that is sustained for periods of less than
one-half cycle.
Single phasing occurs when one
phase is dropped prior to the service
entrance.
~~ 3~
Transients are usually considered
as random voltage pulses of relatively
high magnitude, but short duration,
usually less than about 100 microse-
conds.
Electromagnetic pulse (EMP) is a
single pulse o[ energy created by a
collapsing magnetic field such ae that
created by lightning or a nuclear burst.
The magnitude can vary from insignif-
icant to devastating.
Switching transients are created
by the public utility during load ewitch•
ing or power source switching actions.
They are also the result of other nearby
customers, usually on the same feeder,
switching on and oQ' high-current de-
vices.
A joule is a measure of energy, the
product of volts, amperes and time. It
FIQur~ i
Number of Lightning Days per Year
I Ths probaNNNy of MpMNsp for each day h: Iso number t X65 I
rha m.~e A« th. usn k o.2~ «. probabiBly a rgnts~ on one a.y ouA a ~.
• Flpurs 2
• Sample Surge Voltage as a Function of
Distance from Stroke to Line
2.400
2.000 r+ Mile ~'n ~~^
~c A !Ails
A.600
2 idles
s
. A,200
• .~
~.
0 1 2 J 4 _ 5- e
Tbas M pass
!~ Communieatiom BnRineerinR and Ikaisn June 1987
LIGIITNI NQ
The shape of t~pical lightning
, : stroke current f ow rises rapid y
to its peak and then tapers off
relatively slowly.
is the only true measure of protector
performance. A Watt is the product of
volts and amperes only
Destructive wltage anomalies that
permanently damage connected compo-
nents may be categorized as•naturally
caused or man-made. '1>able 1 lisle
potentially destructive anomalies by
cause.
Natural hamMs
Moat naturally eaused line voltage
anomalies are related to atmospheric
activity of one sort a another. Lightning-
related anomalies can be the result of
either cloud-to-cloud or cloud-to~arth
events. These, in turn, are related to
such factors as the geographical loca-
tion of the site, the ieokeraunic somber
related to that location and the time of
year.
Figure 1 is an ieokeraunic map of the
United States. The number defines the
potential number of lightning days
that can be expected in a year at a
given location. The number can be used
to estimate the probability of lightning
for a given day (if seasons are disre-
garded) and the number of strikes that
may be expected to terminate in any
given area for that year. In applying
these data, two factors moat be consid-
ered: It ie an estimator only and can
vary considerably from year to year,
and it takes only one strike to cause
irreparable damage.
Lightning in general can cause three
specific Corms of hazards: Direct strikes
producing power surges, induced tran-
sients from nearby strikes and the
EMP from the strike's magnetic field.
Power surges result from a direct
strike to any or all phase conductors
near or at some distance from the
facility. The character of these surges
is, therefore, directly related to the
character of the lightning stroke, the
line it strikes and the distance to the
point of concern.'Ib define their specific
character, an engineer must look at
specific cases or parameterize the rise
time, stroke-peak current, distance bet•
weep atrokea and facility or the result-
ing line impedence, and the' grounding
resistances at significant points in
between.
One signifiant factor ie ehawn by
Figure 2 where the Burge voltage ie
estimated for an average lightning
strike Cor various distance from the
station of concern. These numbers
must be greatly increased Cor higher
energy strokes. Other measurements
indicate that these voltages could
achieve levels in excess of 100 Kv if the
wire inaulntion would support that
potential without arcing and if the
measurement point were near the
~ stroke. The higher voltages seem to be
'the norm, rather than the aooeption,
r for FM and TV transmitter sites.
The shape of typical lightning stroke
current fioN- is such that it rises rapidly
to its peak and then tapers oiC rela-
tively slowly, following slog-normal
shaped curve. There are two classes of
lightning atrokea: The impulsive stroke
and the non-impulsive or hot stroke.
This characteristic determines the
damage caused.
The impulsive stroke causes most of
the damage to electronic systems. Since
they embody a large percentage of high
frequency energy, the rate of rise
exceeds 10,000 amperes per micro-
second and can achieve rates of over
100,000 amperes per microsecond. They
last for no more than 100 microseconds.
The non-impulsive or hot stroke
rises much slower than the impulsive ~.
stroke, as low as b00 amperes per
microsecond. However, it usually Isats
much longer, extending out to ea long
as 10 milliseconds to the b0 percentile.
These atrokea are responsible for many
fires and explosions.
Induced transients are the second
order effects of lightning activity in or
near the area of concern. Their charac-
ter is related to the lightning discharge
and the system character into which
the transient is induced. In general,
they are high voltage, low energy
disturbances. Estimates of the poten-
tial for this disturbance phenomenon
range up to 100 Kv. This value is more
dependent upon the system circuit
parameters than lightning itself; inatalla-
LI~:IIININi:
f
Earth-current induced transients
are created by Ilghtning
strikes to earth, to or near the
facility of concern.
tin breakdown levels usually limit the
peak voltages to much lower levels,
except on primary feeders. Public util-
itica have found that tl-is phenomenon
accounts for most of the lightning
faults on lines with a potential of 20
Kv and lower. Lines as short as 60 feet
can pick up a significant transient,
depending on their proximity to the
stroke. These induced transients tend
to take a shape related to the ditTer-
ential of the stroke itself-short nega-
tive and positive pulses of less than 10
joules.
Induced transients are created by
one of three related phenomena. They
are the result of tl-e invisible but
highly potent electrostatic field found
between the charged clouds and the
earth. This field moves and varies in
strength with the charged cloud activ-
ity.
Atmospl-erically induced.transienta
are created by sudden variations in the
electrostatic potential of the atmo-
Fphere. Where the clear air field n-ny
be 150 volts per meter elevation above
earth, during an electrical storm this
field can achieve levels of up to 30,000
volts per meter of elevation. Neartry
cloud-to-cloud and cloud-to-earth dis-
charges can cause significant Held
variations continuously throughout the
storm period, on a random basis, in
both time and magnitude domains.
A Held can be shown where both the
suspended power lines and the inter-
plant data lines experience induced
transients when a charged cloud in the
area oC concern charges everything on
the aurfaoe of the earth beneath it, to
an equal but opposite potential by
induction. The field between tl-e cloud
and earth can achieve 30,000 molts per
meter. A wire elevated above the earth
by 10 meters in this field would be
charged to. a potential -equal to its
surroundings, whichcould theoretically
equal ea much as 300,000 volts witl-
respect to earth. A sudden lightning
THE O10 WAY
Ar~ASr.-
TNf RIGHT WAY
'E1DM-~
THE ONLY TV AUD/O DEV/AT/ON METER MADE fOR CABLE
THE D/GlTAL ANSWER TO AN OLD ANALOG PROBLEM
• Digital Storage Meter
• Predsion Deviatkx~ Calibrator
• Measures Tones or Program Audq
• Measures Peak Deviation •
• Measures RMS loudness
• Measures TV Modulator Unearity
• Measures TV Modulator Frequency Response
• Compares FM Daviatbn on AU_ C~nnels
/NTRODUCTORY PRICE S695. UNT/L AUGUST 1, 1987
CALL YOUR ORDER /N NOWT
FM SYSTEMS, INC.
(7141979-3355 3877 S. Main St. 600-235-6960
Santa Ana, CA 92707
>f0 Communicatimui EnRinecrinx •nd Lheign June 1987 Reader Service Number 17
discharge to earth or another cloud will
cause tl-is field to collapse, leaving the
elevated wire with a bound charge,
~vl-icF- seeks ground through any avail-
able path, even jumping large insula-
tors in the way. This creates a voltage
pulse that can exceed 100.000 volts at
times. 'IYansients resulting from elec-
trostatic field changes can be prop~-
Baled over long distances, depending
on tl-e circuit parameters.
As an example, a nearby cloud-to-
cloud discharge or a strike one mile
away wilt induce as much as ?0 volts
per meter of exposed wire into a thus
connected system.
Earth-current induced transients are
created by lightning strikes to earth,
to or near the facility oCconcern. With
tl-e termination of a stroke to earth all
tl-e charge induced into the earth by
that cloud must move from the point
where it was induced to the point of
impact of the stroke, and thereby
nPUtralize the charge. As a result of
this motion of the induced charge,
earth currents are set up within the
earth's cruet on or near the surface.
Any good conductors buried in the
earth within the charged area will
provide a preferred path for these earth
currents and thus be the recipient of
these eevere earth currents. The results
are transients within the conductor,
either directly or indirectly related to
tl-e earth current character. Current
along the sheath of wires will induce
transients into the inner conductors
through mutual induction, or these
currents will be superimposed on the
conductors without sheaths.
Electromagnetic-field induced tran-
sients are also created by lightning
discharges. Fbr this phenomenon the
IiRI-tning (lash channel acts as a ver•
tical radiator or antenna. The large
flow of current in a short time down the
ionized lightning flash channel sets up
a rapidly changing electromagnetic
field propagating out Crom the stroke
channel in much the same fashion as a
broadcasting station using a single
tower/antenna. These waves propagate
Cor many miles and are the cause of
static in a radio receiver, reelected
waves in the transmitEers and tran-
sients in nearby conductors. Generally,
cloud-to-cloud strokes produce predo-
minately horizontally polarized waves,
~.
..
1.1~:11'I NINA:
Profecllon requirement
9'he protection requirement, if lim-
ited to destructive anomalies, must be
derived from a composite of all the
potentially destructive causes.
A summary of the resulting design
requirements by key design parame-
ters follows:
Peak voltages 45,000 wits
peak-surge current 200,000 amperes
rise-time response 50 nanosernnds
peak-surge energy 100,000 joules
loss of phase 10 cycles or less
mrrwltage line +20 percent
underwltage line -30 percent
It should be understood that it is
possible to enrnunter situations well
beyond these parameters. Aa an exam-
ple, studies have shown that FM radio
and television stations, because of their
location in. remote or elevated areas,
nre subjected to the higher energy
level, fast rise-time surges.
The designer must select the
rfsk considered acceptable and
design the protective system
to satisfy those parameters.
The designer must, therefore, Aelcct
the risk considered acceptable to hi9
client and design the protective system
to satisfy or exceed those parameters.
The foregoing list defines the safe basis
for design. All systems must exceed
that capability by a safe margin and
then Cail-safe for 100 percent pro-
tection.
Protection corrCepts
Lineprvtecrtors faU into three classi fica-
tions: Filtero. surge or transient protec-
tors and voltage regulators or isolation
transformers. The conventional line
filters are primarily limited to the
removal of radio frequency interference
(RFI). Power surges and other distur-
bances are attenuated very little. Line
transformers are available in one or a
combination of tow types: Regulators
or isolation transformers. Regulatore
usually maintain a given output volt-
age over a range of input voltage
variations of up to ±30 percent. The
isolation or super isolation transformer
is a low-pass filter with up to 120 dB of
attenuation across a limited RFI band.
'T'hey do not protect against lightning-
related power surges of significant
magnitude or all modes of noise.
Devices Bold as °eurge protectors"
often have similar, and thus, confusing
claims. They are seldom related to a
well-defined hazard. Any candidate
moat be evaluated against the total
spectrum of performance requirements
as previously defined.
Firnt, how~wer, the applications con-
cept should be considered. There are
tvuo ways of implementing surge pro-
tection into the system to be protected.
The protector may be installed in
parallel with the device to be protected
or it may be installed in series, prior
to the unit to be protected.
Most conventional protectors, except
the LC filters, are designed to be wired
in parallel with the load they protect.
R.i.G.' YERSALIFTS-Ready for You -Right Now!
When you need a lift in a hurry, call
your Versal(it Distributor. He has
fast access to our R.T.G.' pool of
complete, mounted Versallits. No
waiting because of Ivng delivery on
vehicles. manufacturing delays, or
freight problems. Best of all. they're
Versallits, with job-proven
reliability and industry-wide
acceptance. And, since we're
mounting them in quantity, the
illllll
prices are right, too. Truck or van
mounted, telescopic or "elbow"
models, with working heights up to
55 feet. all ready to go to work -
Nowl
,,
`Ready To Go
Mounted on current
model chassis.
t _'
!2 Communicaliom Engineering and Design June 1987
For the name of your
Versalltt Oistritwtor,
calf:
o~
~rrm~
,,~., Kn,.~ ~.~.
P.O. aoa t0]N
w.~e, Tz »~ot-0xt
pal ns~o+oo
-^-~ '','~~ -Reader Service Number 10
•., ; i~ / ~
1•
.~
LIC NTN I NC
The series hybrid protector
r . concept is the only concept
that can be made 100
percent effective.
The parallel protector's efT'ectiveneea
is compromised by two factors:
1. Because it forma a parallel circuit
with the load to be protected, the load
moat share the disturbance it is to be
protected against. As a result, the
protector reaction time is very signif-
icant, as is the clamping ratio (ratio of
peak line wltage to voltage at the
peak-surge current). In actual cases,
measurements have proven to be very
high, in excess of 10 times the normal
line voltage at the peak of the surge.
2. The wiring that connects the paral-
lel protector into the circuit becomes a
aeries impedance to the rapidly clamp-
ing, high surge current, thereby adding
the voltage developed across these
series impedencee to the high clamp
voltage.
By way of contrast, a aeries hybrid
protector is in series with the power
feeding the protected unit, thereby
acting as an interceptor to any incom-
ing disturbances. The negative etTects
of connecting leads, reaction time and
even clamping ratio are overcome
through use of series elements and by
separsting the paths for the surge
current from the clamping control ele-
ments. An examination of the forego-
ing factors alone is sufficient to demon-
strate that the series hybrid protector
rnncept is the only concept that can be
made 100 percent efi'ective.
fut~ Nlminafors
The LEA lJynatech surge eliminator
(SE)O designs are all based on the
same concept, with the acme objectives.
In addition to the previously defined
requirements, the SEa must react wi th i n
6 nanoeeoonda; eliminate at least 99
percent of the possible disturbances for
the particular application without loss
of the protector or protected function;
fail-safe above the 99 percentile by
opening the circuit of the protected
function; and eliminate even the high
frequency, high voltage impulse spike.
'Ib illustrate surge eliminator per-
formance, consider the situation de-
picted in Figure 3. Part A presents a
badly distorted sine wave fora 120-volt
RM3 hot-to-neutral situation where
several forma of voltage anomalies are
illustrated. The equipment destruct
level is assumed to be above about 250
volts peak (to pmtect reliability). The
surge protector must, therefore, pre-
vent the voltage from rising signif-
icantly above that level.
'Ib accomplish this, the SE functions
are ae follows. First, the voltage con-
troller assembly constantly monitors
the output voltage. When it rises above
the clamp voltage, which is usually set
. at 1.2 times the normal peak voltage, it
acts ae a constant voltage device hold-
ing the voltage at the selected clamp
level. If the anomaly is more than a
small transient it turns on the high
energy dissipation assembly. Some of
the energy is dissipated within the unit
TV STEREO
FEATURES INCLUDE:
• Dual Stereo Inputs...for Local Ad
Insertion or Back-up Audio
• Stereo Synthesizer 8uilt~n .
• Separate Video and 4.5 MHz Loop-
throughs
• Level Controls accessible from front
panel
• Deviation Test Tone Built-in
• Self-contained, rack-mount unit. only
1.75 inches high
• Optional Audio Processing (Automatic Gain Controp
.,
1a0 McC~nlek Awnw
Grra Moan, CA s!s=s t.fiAMINc7 IfVOIJsdTTilEB
I714f •7t-4611
nlvx: s1o soo 4as:
.a
Reader Service Number 20
l'~mmunicaliona f:ngineerinR and IhsiRn June 1987 I3
Learning Industries MTS-2 BTSC Stereo Generator, with dbxc9 companding, provides
cable systems with a means to transmit BTSC stereo TV audio.
All SEs are designed with a
special surge fuse that will
open If the capability of the SE
Is exceeded
to compensate for the influence oC the
grounding system surge impedance.
7'lre remainder ie dissipated in the
grounding system and its connections.
During the SE operation, the voltage
to the protected system is maintained
within the operating limits of the
system, neither being crowbarred to or
near ground potential, nor allowed to
rise significantly above the.clamp level.
Aa soon as the surge or transient has
Passed, the SE returns to its passive
mode.
The SE series elements contain a
low-pass filter to accomplish the energy
conservation control functions and min-
imize noise and impulse transients
Negative going spikes on the positi
half-cycles and positive Roing spike
on the negative half-cycles are site
nuated to some degree, about 10 dB.
LEA surge eliminators are designs
to provide rnmplete protection. SF.
wilt handle at least 99 percent of th
potential surges or transients the
vwuld experience in a particular appl ica-
tion. Beyond that, all SEe are designed
with a special surge fuse that will open
if the capability of the SE is exceeded.
Note that the fuse-blow characteristic
ie a decaying exponential that asymp-
totically approaches the circuit operat-
FIGURE 3 ~ •
Surge Eliminator Protect(ve Action
8elore ProteMlon
• ~ ••Destruclive Surges
---~r-_t_1-----~----~-----------
tss---1~.-J-_...r------I~---~----~-~ - --
,~
-tti6---- - - -- -----
----rr---------
-cw-~.-----r-----. L-- --...-----~
B. Aller Proteclbn
.200- .Clamp Level
--~---~-1-----rst-------------
I~t66--
Note tlphl Clamp
- '~'-tt------ ~~-----
-- ' --
. s
;~ /
-200 --- -- - - - . -- -v ~ - ~ - - -Clamp level
ing current. The SE will dissipate any
ve energy below the curve and above the
s operating current level and the fuse
will protect against any unusual event
that would introduce energy in excess
d of the SE capability. The probability
s for this event ie leas than one chance
e in 10 years for the average location
y within the continental United States.
The rating of SEs in terms of power
handling capabilities is not a simple
matter. Although SEa can dissipate
energies in excess of 100,000 joules per
phase and handle surge current (lows
in excess of 200,000 amperes, this does
not completely describe the protection
provided. The LEA SE design is such
that it makes use of the grounding
resistance and power system surge
impedance to increase the overall pro- ~
tection capability significantly. The
principle can be illustrated in which a
worst case lightning strike of 200,000
amperes is assumed to have terminated
at a hilltop utility pole. The pole is
assumed to be within 35 meters of the
users terminal wherein a LEA SE is
used Cor surge protection. The parame-
ters selected are typical fora moun-
taintop facility, or perhaps a bit on the
optimistic aide. Referring now to the
related equipment schematic diagram,
it may be seen that both the surge
impedance of the connecting wiring
and the grounding resistance are used
to dissipate a major portion of the
stroke released energy, moat of which
is in the grounding resistance. That ie,
the excess energy heats up the earth
around the grounding components. Flom
these data it is evident that the SE
could provide protection against light-
ping induced energy levels in excess of
a total of 100,000 joules.
The clamping ratio (CR) is also a
factor oC importance in rnnaidering a
surge protector. The CR is defined ae
the ratio of line wltage under the worst
case lightning surge current va. the
initial clamping level. Fbr all surge
protectors the terminal voltage permit-
red at the protected equipment rises
with a rise in surge current. Obviously,
the Tower the CR value the safer the
protected unit ie for any given set oC
rnnditions. ' ~
This article will appear in three
aeclions, ending with August. Part 2
next month: Now to cope with direct
strikes.
~•
~~ Communicaliona EnRineerinR and DeeignJune 1987
I
~,
July 15, 1988
Mr. Michael J. Kelly
>?. 0. 13ox 655
Riclunond, Virginia 23219
Dear Mr.Kelly:
~~~9~~~
We are the owners of Office Condominiums located on Twinridge Lane, Chesterfield
County, Va. We have indicated, in yellow, on the attached County of Chesterfield
Tax Map 18-15, the location of our properties.
An application made to the County of Chesterfield by Contel Cellular, Inc, requests
permission to install a 198 foot Conrnrunications Tower in one of two locations as
shown in red and blue on the enclosed Chesterfield County Tax Maps, 18-15 and 18-16.
In either of the proposed locations you can readily see the nearness of such locations
to .our ,off ice buildings.
7.'he area in which permission is requested to locate such a tower is composed, almost
;entirely, of residential, office and quiet retail use. Certainly to ask to intrude
.into such a highly developed area with such a tower is inappropriate.
Collectively we have an investment in the Twinridge Condominium Office Development
of approximately $ 2,295,000.00 To consider placing such an installation as
this tower as close to our development as has been requested, and in constant view,
is extremely objectionable to us. '1'he applicant should be required to acquire a
location where the location of such an installation would not act to adversely affect
the value of properties that have been developed in the immediate area. In addition
the presence of such a tower in either of the proposed locations will certainly tend
to neutralize the aesthetic appeal of all of the properties in the area.
We ask that you assist us in protecting our properties by voting to oppose the locating
of this co;rimunications tower in either of the proposed locations.
r-
~,
!~...
ame (s) ~
~~
LS ( ~l
Address ~(,~
Telephone
Name(s)
Address
Telephone
~'.~,~-
,,~77 - ~os-~
Telephone
Name (s
/., ~--
w7 ~W I N ~ ac' I aw-~
Address
Telepho e
-_:_---/
~~ y`~
Address ~'
~1
July 15, 1988
Mr. Michael J. Kelly
P. 0: Box 655
Rictunond, Virginia 23219
Dear Mr.Kelly:
We are the owners of Office Condominiums located on Twinridge Lane, Chesterfield
County, Va. We have indicated, in yellow, on the attached County of Chesterfield
Tax Map 18-15, the location of our properties.
An applical-ion made to the County of Chesterfield by Contel Cellular, Inc. requests
permission to install a 198 foot Conununications Tower in one of two locations as
shown in red and blue on the enclosed Chesterfield County Tax Maps, 18-15 and 18-16.
In either of the proposed locations you can readily see the nearness of such locations
to our office buildings.
The area in which permission is requested to locate such a tower is composed, almost
entirely, of residential, office aiid quiet retail use. Certainly to ask to intrude
into such a highly developed area with such a tower is inappropriate.
Collectively we have an investment in the Twinridge Condominium Office Development
of approximately $ 2,295,000.00 To consider placing such an installation as
this tower as close to our development as has been requested, and in constant view,
is extremely objectionable to us. The applicant should be required to acquire a
location where the location of such an installation would not act to adversely affect
the value of properties that have been developed in the immediate area. In addition
the presence of such a tower in either of the proposed locations will certainly tend
to neutralize the aesthetic appeal of all of the properties in the area.
We ask that you assist us in protecting our properties by voting to oppose the locating
of this conununications tower in either of the proposed locations.
Very truly yours,
~ ~~ti
Name (s)
~ ~2
Name s)
,jG~" ~~1`L~sivllfa6a LA. ~incr-~ yr L323r
Address
r;:
~,
~: 2.7 z.-7S 9 3
Telephone
~.
.n ~fi
~' Name(s)
Address
Telephone
~o ,~ ~~/~.~, ~~u, ~3y3 r
Address
Telephone
.r
Name ~% A~ ~~Y~~
Address
~~~- 7~7J
Telephone
llate
hlr. Michael J. Kelly
P. 0. Box 655
Richmond, Virginia 23219
Dear Mr. Kelly;
We are writing you, as the riidlothian Representative of the Chesterfield
County Planning Commission, to express our grave concern regarding tite
application by Contel Cellular, Inc. for permission to erect a 198 foot
coirnnunications tower in one of two proposed locations, referred to in the
application and as indicated on the County of Chesterfield Tax Map 18-15.
We, the undersigned, the parents, and in some cases the grandparents, of the
children attending The Good Shepherd Christian U:ry Care Preschool facility at
100 Buford Road. One of the proposed locations for the Tower is in[mediately
at the rear of the play area for our children. '11te other location is very
close by.
As you know there is st-i11 a difference of opinion among the experts
in the scientific field regarding the effects of Microwaves on the
h wnan body, In addition to this possible detrimental effect on our
children we are concerned for tltelr safety it t-he proposed 198 foot
tower is installed and shou:Ld fall.
While :i.t will be a great inconvenience for us to transfer our children
to anoL-her facility, because of the distance involved from our homes,
and certainly disastrous economically to the operators of this well
operated facility, we will remove our children from this facility if
approval is given for Che er.ectio^ of this Cvt[mtunications Tower in
either of the proposed locations referred to in the applications of
Contel Cellular.
We earnestly and respectfully ask that you not approve either of these
requests.
Very truly yours,
/ ~
Name ) Name(s)
~~~- l I~e--l~-o-c9. ~
Street Address
Street Address
~~- ~~7d
Te lepltone
~~G-oy6/
Telephone
C -'
__L_~
Na e(s) Name(s)
Street Address
Stre t Address
' Page 2
i
Letter to Mr. Michael J. Ke11y from the parents of children attending The
Good Shepherd Christian Day Care Preschool facility at lU0 Buford Road (continued)
Name (s)
9~'iy ~~d. ~ .
Stree/~ress
J ~•~.. a 3 ~~s
~a ~ -a ~~ - ~~ s-g
Telephone
Name(s) ~)~~ 1_rY1~JPC~, v,~-I3~3~a1~
~ ~ ~ ~~~~a~~ '~~
~'er`~~~°~s'1
Street Address
Telephone
~ ~/1'~-/
~~
Name(s)
~~-
Street Address
g~~-3~ -s~c~~
Telephone
Name (s)
Street Address
_~7~- ~o L ~. ___
Telephone
%~ ~~ ham. ~cQ Ca~!~ _
Name(s)
Street Address
-____~`
1
a e(s)
~aO ®~o ~~r~-r ~ wc, ~ .
Street Address
~g~-o9~L
'Telephone
~~ ~ 'Lt ` /C / /' -~r~ Azyl
.,
ame _s
~~ Cd ~ ~~~li~
~c~ ~ ~ _
Street Address
Telephone
~ ~~~ ~ ~~
Name(s)
~1~~~ ~-
Street Address
a-~ v~~~ ~
Telephone
~ ~~~ ~
Name ( )
~s73 ~ CMG: ,_ l~~
Street Address
'Telephone
/Uoic~. J. /y1as~
Na-ne (s)
Street Address
Page 3
`,~ )
Letter to Mr, Michael J,-Kelly from the parents of children attending The
Good Shepherd Christian Day Care Preschool facility at 100 Buford Road (continued)
Name (s)
Street Address
~--~L - 3 t, ~~
Telephone
~~2he~ d ~~ "`~
Name(s)
~~~ S ~~ ~
Street Addres
~~u-1U~~
Telephone
Name(s)
079// ~'- ~6~/ ~~- ,C'-,~- I~
Street Address
'1'e 1 e phone
/ ~ '
~~ W
e s)
/ ~~yl~c.~.. ~,~ .
Street Address
// 'Telephone
J
~o yCe ~ ~ ~~Ll.~g-~~-Y
Name(s)
Street Address
x'72-2~c~ ~
Telephone
~~U Z.~/
Name(s)
Street Address
't'elephone
1/. ~~
Name (s)
Street Address
Telephone /
~/ ./
Name( )
l~ s a-
tre t Addr
c.~ yd ~ ~ ~ ~ 9'9X ~J; ~~ ~s ~R .
Name(s) /
Street Address
/Telephone
F- . 1`s Q ~
Name (s)
~v i ~~--~~ Q ~~~~
Street Address
Pa€,e 4
Letter to Mr.
Michael J.
Ke11y from the parents of i
chi. ].dren'attending
The
Good Shepherd Christian Day Care Preschool facility at- 100 Buford Road (continued)
Z - -a-• IA- c... /.
Fit IBS N-~4- L
Name (s)
L~ 3~--5 J~~k~ NS ~ _
Street Address
_a-76 - `~6/~
Telephone
Y
~_ ~~ U
Name(s)
~ ~ w ~~ ~~~.,c~ ~ c~~r
Street Address
~~ ~~ ~~ ~
Telephone
Name(s) 1
c,..
_ . ~._..
Street Address
,.
Telephone j
C~- ,
N:~me (s)
ame(s)
.. ~ n~
Gc
Strellet Address
r
J
_. _ ~ P
(~, ~_
// 1'e le phone
~_
Name(s)
~'~7oC~ ~a-~l~l~a~ti (},'tee ~_e_
Street Address
~7~~~- ~~' 1 y~
elephone
~~a~~~~~.o~ ~ ~~ ~~~~.~
Name(s)
/'7 ~
~ J (.~i~J7ZL,DZ 1
Street Address
~ y y z ~ m ~~wc~ ~~ ~,~
Street Address
2 72 - ~~s'
Telephone
I ~ ~~ _
' ~ ~~~
Name(s)
Street Address
Telephone
./;
r_ _ - r'
N me (s)
r ~ ~ ~~
Street Address
._._.~
~) ~~ rte/ - L ~ `~ ~ G~
1'e lephone
~ ~ ~~ ~ o _
Name (s)
~ ~c~o ~ ~~.as2. l-, n
Street Address
' Page 5 ,,1
Letter to Mr. Michael J. Kelly Lrom the parents of children attending The
Good Shepherd Christian Day Care Preschool facility at l0U Buford Road (continued)
c. ', ~ ~ ~~
Name (s) '~
( , ~ ` , ,, ' 1 ' r rr r
l
=~ ~ ~
Street Address
' ) l
_~ ~ ~ r .~
Telephone '
~ /
U`" "`'`.
Name(s)
Z~~ ~~~~
Street Address
'1'e le phone
~ ~ ( ~ /
~ t ~ ~ , i ~ i , :1 ,~ , ~,_ ~.: 1
Name(s)
Street Address
i'e 1 ephone
Name(s)
Street Address
Sao ~ ~I ~ ~-
Telephone
Name(s)
Street Address
Name(s)
Street Address
'1'e lephone
Name(s)
Street Address
Telephone
Name(s)
Street Address
'Telephone
Name(s)
Street Address
7'e lephone
Name (s)
Street Address
°
Page 6 ~a
Letter to Mr. Michael J. Kelly from the parents of children1attending The
Good Shepherd Christian Uay Care Preschool facility at 100 Buford Road (continued)
~e(s) Name(s)
3 ~ 1 ~~ ~ i ~
i /
/~
~
~
l
.
~ ,
oc
~ /
r
Street Address .
Street Address
Telephone 'Telephone
Name(s)
Name(s)
Street Address
Street Address
Te]-ephone
Telephone
Name(s) Name(s)
Street Address Street Address
Telephone 'Telephone,
Name(s) Name(s)
Street Address Street Address
Telephone Telephone
Natne (s) Name (s )
Street Address Street Address
fnnml Crllular of Viryinia, Inc.
1104 West Laburnum Avenue
Suite; iU4
Aiclnnund, VA 23271
804 3!ib k1!iUU
== =-=~ CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
Address
7
~DL.
'~ ~~ Garr rr~°°...,,.~ r-ir . /7" V !4 ; j ~ 3
~ ~~
f ~ ti' ;.
i~ s~ l C~.~'~~-. yc~ z 3 ~-_~
~,
Z,3 2 3~
2~! / 5
3~
Cuntcl Crllular of Virginia, Inc.
2104 West Laburnum Avenue
Suite lU4
Hichmand, VA 23227
1104 3!i5 U5UII
== CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area..
Name
t . ;'~.
~}'~ (~,~-~,~.~ ~) ~(~, ' ~~~ rte;
Address
r~; e - ~~
^~ 1, ;;
r,r,~
~ ~ ~ ~
.r:
5-Io'a l~ ~`l/ /4~<r <<'~-r~P ~ 32,E
~~a~ y'_ ~~~~~~~ ~~x. ~ ~3 ~~~ ~
~ -- ~ ~ ,
- ~ - -- --
Z~f
._- -~
Coinel Crllnloi of Viryiniu, Inr;.
71(14 V~Ie;i Lal~wnum AVL'rIUC
Suilr, lll4
Hiclunund, V/1 73221
O(14 356 U;~IIII
--==-== CELLULAR
To the Chesterfield County Board of Supervisors:
Tfle undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that ire support Contel Cellular's request to construct
a telecornnlunications tower on either Nortfr Providence Road or Buford Road, as
the presence of a tower on either site ~,~ill substantially improve the quality
of cellular service in the area.
Name
~ r~ ,~,
Address
Cumcl CclUdar of Viryinia, Inc.
2104 West Lahurnurn Avenue
Suite lU4
Richmond, VA 23727
004 355 0500
== CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
Name o
~~~~ ~~ ~
//;; r ~, y„
/ UfoG ~ P :~T J~~,~ ~d d
a~3 / ~2i sfw~ o ~D~e4'~ ~,~ ~~r e~~r,/a3j3/
r ~
-C ) ~/'
-~~ _
Address )~
- - ~~ !~~ .
~~' i
__
Guucl Cnllulor n( Vir~inin, Inc.
2104 West Laburnum Avenue
Suite 104
Richmond, VA 23227
1104 3!i5 0!i00
== CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road,. as
the presence of a tower on.,either site will substantially improve the quality
of cellular service in the area.
Address
2 9 sa c%o a aRi;d ~E fin. IDf,e M,v~~~y.., .
~'~_~ e~N e c ~9ryPd ,E''c.h nta~ fin.
a~ 3n l~~« s-f ea dl ~ ~ . r~ ~ d I o . 1/a
~ ~
2. s !,3
~ Z o o <. z
30(~ U '0 ' ~ Gf~.~~~ Z3~~
Y! ~ J
r/,zfj~
~~
l(.1
a31~
~v~
Name
Cuuuil I;elhd.u of Virginia, Inr.
2101 Wesr l~hurnum Avrnuc
$uilr' iDd
Ilichnn~rrrl, V11 23221
}liVi :155 ~~,np
~,«___-
~`---~~~ CELLULAR
To the Chesterfield County Board of Supervisors:
Tfie undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Celiular's request to construct
a telecommunications tower on either North Pravidence Raad or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
~..
,111E-:: i -.3~: blED '? :4~3
Address
11l/~~ ~~`.~.
~ 313
SRr,, ~
~ l o~ ~L..~~.tes~~D~ ~ ~ roLcc~r ~ :~3,3
.~~.~~.-
1 ~) I +-~- I L~ ~c~
/~a~a
~1. t~-(a~~ 10 . /~ ~ 23/lz
~'1..~i~/~~u~~31! z
+'+ TC~THL PH~:~E . `r'te '+ +
pp _ ~i v
Canlcl Cclhdar of Viryinio, Inc.
2104 West Laburnum Avenue
Suite lU4
Richmond, VA 23227
UU4 3!iU E{`,dl(I
== CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
Address
~ 7 L.M GJDU ~f C /J ; ~ 9 ~S l ~2
~~~ 1,,/
~o ~ ~~
Cunicl Crllnlar ul Virpinin, Inr..
2104 West Laburnum Avenue
Suilu 104
Richmond, VA 23227
004 355 flhll0
-_= CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
Name f
~,ff ~.. l~
_. f=
~ ~ /
w~.
Address
~// /
7
:'~r"~C ; ,~„ l% ~--~ ,r N C' - I ~ ~ ~~.~s t-E'er'
Conlel Cclhdnr of Virginia, Inc.
2104 West Laburnum Avenue
Suiia lU4
Richmond, VA 23221
U114 3!i5 UbUU
== CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
Name
Address
~ ~ Z- ~ 2,u c.~~o ~', .., E~i-L, N. ~ ~.3Z3S
~~~3 - iOAaJ ~ vti.- ~ ,PL~~i
~CJ~.J 7 ~ l_ I~7 1lA~L
a
- ~~~
L C',1
~, To ~-he, C~h ~s~(-e~'-~i ~lc~ ~,Q~_~oox-d y-F ~t ,~r~ ~- y i s o r s
Tl~e. v~rd~ars ~ a ~~~ r e 5 i d.e_n--Fs o-~ C.hes-Fe...r-~' -el d
'',S~ ~,,.tr,-F,~ we°S~, -{D i ~c~c'r n~P ~-~,a~t c,V~. sc~..poo~
w~t-~~ C ~ - c ~ - ~„ r `s r~e~ e s -f r~ c~r,.st r c.~ ~-~ a
-~ ~~ ~ ~~ n-. ~,, c a /1 ~ r cx ~1 Ln s `~'bll~x' j~'1 ~c'"~'V~ L1r ~ O~"`l-~n
~ro ~ i d rn ~ R ~ ~~ 3 u ~~d P d ^Tl~e- .~ r~.~ 2.t~ C~ c)f a
r~~ ~u5 -~r~ u~r t~1 ~ S l,~c-Frx r~,'a l C~ c i +~ ~rU~12
'~ ' ~-- r~
~ ~ r -
_ ~ ,
p,.
~Z3
{a
3 ~
~ddd
4
~~~
~~~~~~
,,
z ~ ~
B
a ~~~ ~ c~ s-e ~C
Contcl Cellular of Virginia, Inc.
2104 West Laburnum Avenue
Suite 104
Richmond, VA 23227
E304 3!i5 A500
-~ CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
Nam Address
n ,
Contel CEllular of Virginia, Inc.
210h West Laburnum Avenue
SUIfE ~()~
Richmond, VA 23777
BOh 3!i5 8500
=~ CELLULAR
To the Chesterfield County Board of Supervisors:
The undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contel Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
3
Cliulol I;CISi',li 01 `ihi,~iniil, IN;.
2101 West lahurnum Avonue
$~litc 1D4
Hhhn!w~d, VA 23221
f11N ;155 f3'.~OIM
'~--~-~~. CELLIJLA
~~ a= = _ - R
Ta ttre Chesterfield County Board of Supervisors:
Tf+e undersigned residents of Chesterfield County wish to indicate to the
Board of Supervisors that we support Contei Cellular's request to construct
a telecommunications tower on either North Providence Road or Buford Road, as
the presence of a tower on either site will substantially improve the quality
of cellular service in the area.
TI_~l_-.:?_,,.:, tdEIl .=±:44 Ltr_t:} .3~5 91?':~ F'.c~2
Address '~ /~ _/